Chapter 1 Circuit Measurement

p. 10

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-1 UNCLASSIFIED 1 CIRCUIT MEASUREMENT LEARNING OBJECTIVES

Learning objectives are stated at the beginning of each chapter. These learning objectives serve as a preview of the information you are expected to learn in the chapter. The comprehensive check questions are based on the objectives. By successfully completing the NRTC, you indicate that you have met the objectives and have learned the information. The learning objectives are listed below.

Upon completion of this chapter you will be able to:

1. State two ways circuit measurement is used, why in-circuit meters are used, and one advantage of out-of-circuit meters. 2. State the way in which a compass reacts to a conducting wire including the compass reaction to increasing and decreasing dc and ac high and low frequencies. 3. State how a d’Arsonval meter movement reacts to dc. 4. State the purpose of a rectifier as used in ac meters. 5. State the meaning of the term "damping" as it applies to meter movements and describe two methods by which damping is accomplished. 6. Identify average value as the value of ac measured and effective value (rms) as the ac value indicated on ac meter scales. 7. Identify three meter movements that measure dc or ac without the use of a rectifier. 8. State the electrical quantity measured by an ammeter, the way in which an ammeter is connected in a circuit, and the effect of an ammeter upon a circuit. 9. Define ammeter sensitivity. 10. State the method used to allow an ammeter to measure different ranges and the reason for using the highest range when connecting an ammeter to a circuit. 11. List the safety precautions for ammeter use. 12. State the electrical quantity measured by a voltmeter, the way in which a voltmeter is connected in a circuit, the way in which a voltmeter affects the circuit being measured, and the way in which a voltmeter is made from a current reacting meter movement. 13. Define voltmeter sensitivity. 14. State the method used to allow a voltmeter to measure different ranges and the reason for using the highest range when connecting a voltmeter to a circuit. 15. Identify the type of meter movement that reacts to voltage and the most common use of this movement. 16. List the safety precautions for voltmeter use. 17. State the electrical quantity measured by an ohmmeter, the second use of an ohmmeter, and the way in which an ohmmeter is connected to a resistance being measured. 18. State the method used to allow an ohmmeter to measure different ranges and the area of an ohmmeter scale that should be used when measuring resistance.

p. 11

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-2 UNCLASSIFIED 19. State the two types of ohmmeters and the way in which each can be identified. 20. List the safety precautions for ohmmeter use. 21. State the primary reason for using a megger and the method of using it. 22. Identify normal and abnormal indications on a megger. 23. List the safety precautions for megger use. 24. State how a multimeter differs from other meters, the reason a multimeter is preferred over separate meters, and the way in which a multimeter is changed from a voltage measuring device to a current measuring device. 25. State the reason the ac and dc scales of a multimeter differ, the reason for having a mirror on the scale of a multimeter, and the proper way of reading a multimeter using the mirror. 26. List the safety precautions for multimeter use. 27. State the purpose of a hook-on type voltmeter. 28. State the electrical quantity measured by a wattmeter and a watt-hour meter. 29. Identify the two types of frequency meters. 30. Identify the type of meter and interpret the meter reading from scale presentations of an ammeter; a voltmeter; an ohmmeter; a megger; a multimeter (current, voltage, and resistance examples); a wattmeter; a watt-hour meter; and a frequency meter (vibrating reed and moving-disk types).

1.1 INTRODUCTION This chapter will acquaint you with the basics of circuit measurement and some of the devices used to measure voltage, current, resistance, power, and frequency. There are other quantities involved in electrical circuits, such as capacitance, inductance, impedance, true power, and effective power. It is possible to measure any circuit quantity once you are able to select and use the proper circuit measuring device. You will NOT know all there is to know about circuit measuring devices (test equipment) when you finish this chapter. That is beyond the scope of this chapter and even beyond the scope of this training series. However, more information on test equipment is provided in another portion of this training series.

A question which you might ask before starting this chapter is "Why do I need to know about circuit measurement?"

If you intend to accomplish anything in the field of electricity and electronics, you must be aware of the forces acting inside the circuits with which you work. Modules 1 and 2 of this training series introduced you to the physics involved in the study of electricity and to the fundamental concepts of direct and alternating current. The terms voltage (volts), current (amperes), and resistance (ohms) were explained, as well as the various circuit elements; e.g., resistors, capacitors, inductors, transformers, and batteries.

p. 12

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-3 UNCLASSIFIED In explaining these terms and elements to you, schematic symbols and schematic diagrams were used. In many of these schematic diagrams, a meter was represented in the circuit, as shown in figure 1-1.

As you recall, the current in a dc circuit with 6 volts across a 6-ohm resistor is 1 ampere. The @ (UPPERCASE A) in figure 1-1 is the symbol for an ammeter. An ammeter is a device that measures current. The name "ammeter" comes from the fact that it is a meter used to measure current (in amperes), and thus is called an AMpere METER, or AMMETER. The ammeter in figure 1-1 is measuring a current of 1 ampere with the voltage and resistance values given.

Figure 1-1 A simple representative circuit

p. 13

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-4 UNCLASSIFIED 1.2 INTRODUCTION TO CIRCUIT MEASUREMENT Circuit measurement is used to monitor the operation of an electrical or electronic device, or to determine the reason a device is not operating properly. Since electricity is invisible, you must use some sort of device to determine what is happening in an electrical circuit. Various devices called test equipment are used to measure electrical quantities. The most common types of test equipment use some kind of metering device.

1.2.1 In-Circuit Meters Some electrical and electronic devices have meters built into them. These meters are known as in-circuit meters. An in-circuit meter is used to monitor the operation of the device in which it is installed. Some examples of in-circuit meters are the generator or alternator meter on some automobiles; the voltage, current, and frequency meters on control panels at electrical power plants; and the electrical power meter that records the amount of electricity used in a building.

It is not practical to install an in-circuit meter in every circuit. However, it is possible to install an in-circuit meter in each critical or representative circuit to monitor the operation of a piece of electrical equipment. A mere glance at or scan of the in-circuit meters on a control board is often sufficient to tell if the equipment is working properly.

While an in-circuit meter will indicate that an electrical device is not functioning properly, the cause of the malfunction is determined by troubleshooting. Troubleshooting is the process of locating and repairing faults in equipment after they have occurred . Since troubleshooting is covered elsewhere in this training series, it will be mentioned here only as it applies to circuit measurement.

1.2.2 Out-of-Circuit Meters In troubleshooting, it is usually necessary to use a meter that can be connected to the electrical or electronic equipment at various testing points and may be moved from one piece of equipment to another. These meters are generally portable and self-contained, and are known as out-of-circuit meters.

Out-of-circuit meters are more versatile than in-circuit meters in that the out-of-circuit meter can be used wherever you wish to connect it. Therefore, the out-of-circuit meter is more valuable in locating the cause of a malfunction in a device.

p. 14

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-5 UNCLASSIFIED Q1. What are two ways that circuit measurement is used? Q2. Why are in-circuit meters used? Q3. What is one advantage of an out-of-circuit meter when it is compared with an in- circuit meter? 1.3 BASIC METER MOVEMENTS The meter movement is, as the name implies, the part of a meter that moves. A meter movement converts electrical energy into mechanical energy. There are many different types of meter movements. The first one you will learn about is based upon a principle with which you are already familiar. That principle is the interaction of magnetic fields.

1.3.1 Compass and Conducting Wire You know that an electrical conductor in which current flows has a magnetic field generated around it. If a compass is placed close to the conductor, the compass will react to that magnetic field (fig. 1-2).

If the battery is disconnected, the north end of the compass needle will point to magnetic north, as illustrated in figure 1-2(A) by the broken-line compass needle pointing to the right. When the battery is connected, current flows through the circuit and the compass needle aligns itself with the magnetic field of the conductor, as indicated by the solid compass needle. The strength of the magnetic field created around the conductor is dependent upon the amount of current.

In figure 1-2(A), the resistance in the circuit is 6 ohms. With the 6-volt battery shown, current in the circuit is 1 ampere. In figure 1-2(B), the resistance has been changed to 12 ohms. With the 6-volt battery shown, current in the circuit is 1/2 or .5 ampere. The magnetic field around the conductor in figure 1-2(B) is weaker than the magnetic field around the conductor in figure 1-2(A). The compass needle in figure 1-2(B) does not move as far from magnetic north.

If the direction of the current is reversed, the compass needle will move in the opposite direction because the polarity of the magnetic field has reversed.

In figure 1-2(C), the battery connections are reversed and the compass needle now moves in the opposite direction.

p. 15

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-6 UNCLASSIFIED

You can construct a crude meter to measure current by using a compass and a piece of paper. By using resistors of known values, and marking the paper to indicate a numerical value, as in figure 1-3, you have a device that measures current.

This is, in fact, the way the first GALVANOMETERS were developed. A galvanometer is an instrument that measures small amounts of current and is based on the electromagnetic principle. A galvanometer can also use the principles of electrodynamics, which will be covered later in this topic.

Figure 1-2 Compass and conductor with direct current

p. 16

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-7 UNCLASSIFIED The meter in figure 1-3 is not very practical for electrical measurement. The amount the compass needle swings depends upon the closeness of the compass to the conductor carrying the current, the direction of the conductor in relation to magnetic north, and the influence of other magnetic fields. In addition, very small amounts of current will not overcome the magnetic field of the Earth and the needle will not move.

Q4. How does a compass react when placed close to a current carrying conductor? Q5. If the amount of current in the conductor changes, what happens to the magnetic field around the conductor? Q6. How does the compass needle react to a decreased magnetic field?

Figure 1-3 A simple meter from a compass

p. 17

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-8 UNCLASSIFIED 1.3.2 Permanent-Magnet Moving-Coil Movement The compass and conducting wire meter can be considered a fixed-conductor moving- magnet device since the compass is, in reality, a magnet that is allowed to move. The basic principle of this device is the interaction of magnetic fields-the field of the compass (a permanent magnet) and the field around the conductor (a simple electromagnet).

A permanent-magnet moving-coil movement is based upon a fixed permanent magnet and a coil of wire which is able to move, as in figure 1-4. When the switch is closed, causing current through the coil, the coil will have a magnetic field which will react to the magnetic field of the permanent magnet. The bottom portion of the coil in figure 1-4 will be the north pole of this electromagnet.

Figure 1-4 A movable coil in a magnetic field (no current)

p. 18

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-9 UNCLASSIFIED Since opposite poles attract, the coil will move to the position shown in figure 1-5.

The coil of wire is wound on an aluminum frame, or bobbin, and the bobbin is supported by jeweled bearings which allow it to move freely. This is shown in figure 1-6.

Figure 1-5 A movable coil in a magnetic field (current) Figure 1-6 A basic coil arrangement

p. 19

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-10 UNCLASSIFIED To use this permanent-magnet moving-coil device as a meter, two problems must be solved. First, a way must be found to return the coil to its original position when there is no current through the coil. Second, a method is needed to indicate the amount of coil movement.

The first problem is solved by the use of hairsprings attached to each end of the coil as shown in figure 1-7. These hairsprings can also be used to make the electrical connections to the coil. With the use of hairsprings, the coil will return to its initial position when there is no current. The springs will also tend to resist the movement of the coil when there is current through the coil. When the attraction between the magnetic fields (from the permanent magnet and the coil) is exactly equal to the force of the hairsprings, the coil will stop moving toward the magnet.

As the current through the coil increases, the magnetic field generated around the coil increases. The stronger the magnetic field around the coil, the farther the coil will move. This is a good basis for a meter.

Figure 1-7 Coil and hairsprings

p. 20

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-11 UNCLASSIFIED But, how will you know how far the coil moves? If a pointer is attached to the coil and extended out to a scale, the pointer will move as the coil moves, and the scale can be marked to indicate the amount of current through the coil. This is shown in figure 1-8.

Two other features are used to increase the accuracy and efficiency of this meter movement. First, an iron core is placed inside the coil to concentrate the magnetic fields. Second, curved pole pieces are attached to the magnet to ensure that the turning force on the coil increases steadily as the current increases.

Figure 1-8 A complete coil

p. 21

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-12 UNCLASSIFIED The meter movement as it appears when fully assembled is shown in figure 1-9.

This permanent-magnet moving-coil meter movement is the basic movement in most measuring instruments. It is commonly called the d’Arsonval movement because it was first employed by the Frenchman d’Arsonval in making electrical measurements. Figure 1-10 is a view of the d’Arsonval meter movement used in a meter.

Figure 1-9 Assembled meter movement

p. 22

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-13 UNCLASSIFIED

Q7. What type of meter movement is the d’Arsonval meter movement? Q8. What is the effect of current flow through the coil in a d’Arsonval meter movement? Q9. What are three functions of the hairsprings in a d’Arsonval meter movement?

Figure 1-10 A meter using d’Arsonval movement

p. 23

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-14 UNCLASSIFIED 1.3.3 Compass and Alternating Current Up to this point, only direct current examples have been used. What happens with the use of alternating current? Figure 1-11 shows a magnet close to a conductor carrying alternating current at a frequency of 1 hertz.

The compass needle will swing toward the east part of the compass (down) as the current goes positive, as represented in figure 1-11(A). (The sine wave of the current is shown in the lower portion of the figure to help you visualize the current in the conductor.)

In figure 1-11(B), the current returns to zero, and the compass needle returns to magnetic north (right). As the current goes negative, as in figure 1-11(C), the compass needle swings toward the west portion of the compass (up). The compass needle returns to magnetic north as the current returns to zero as shown in figure 1-11(D).

This cycle of the current going positive and negative and the compass swinging back and forth will continue as long as there is alternating current in the conductor.

Figure 1-11 Compass and conductor with ac

p. 24

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-15 UNCLASSIFIED If the frequency of the alternating current is increased, the compass needle will swing back and forth at a higher rate (faster). At a high enough frequency, the compass needle will not swing back and forth, but simply vibrate around the magnetic north position. This happens because the needle cannot react fast enough to the very rapid current alternations. The compass (a simple meter) will indicate the average value of the alternating current (remember the average value of a sine wave is zero) by vibrating around the zero point on the meter (magnetic north). This is not of much use if you wish to know the value of the alternating current. Some device, such as a rectifier, is needed to allow the compass to react to the alternating current in a way that can be useful in measuring the current.

1.3.4 Rectifier for AC Measurement A rectifier is a device that changes alternating current to a form of direct current. The way in which this is done will be covered later in this training series. For now, it is necessary to know only the information presented in figure 1-12.

Figure 1-12 shows that an alternating current passed through a rectifier will come out as a "pulsating direct current."

Figure 1-12 Rectifier action

p. 25

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-16 UNCLASSIFIED What happens to the compass now? Figure 1-13 answers that question.

When the compass is placed close to the wire and the frequency of the alternating current is high enough, the compass will vibrate around a point that represents the average value of the pulsating direct current, as shown in figure 1-13.

Q10. How would a compass react when placed close to a conductor carrying alternating current at a low frequency? Q11. How would the compass react if the alternating current through the conductor was a high frequency? Q12. What is the purpose of a rectifier in a meter?

Figure 1-13 Compass and conductor; rectified ac

p. 26

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-17 UNCLASSIFIED By connecting a rectifier to a d’Arsonval meter movement, an alternating current measuring device is created.

When ac is converted to pulsating dc, the d’Arsonval movement will react to the average value of the pulsating dc (which is the average value of one-half of the sine wave). Another characteristic of using a rectifier concerns the fact that the d’Arsonval meter movement is capable of indicating current in only one direction. If the d’Arsonval meter movement were used to indicate alternating current without a rectifier, or direct current of the wrong polarity, the movement would be severely damaged. The pulsating dc is current in a single direction, and so the d’Arsonval meter movement can be used as long as proper polarity is observed.

1.3.5 Damping A problem that is created by the use of a rectifier and d,Arsonval meter movement is that the pointer will vibrate (oscillate) around the average value indication. This oscillation will make the meter difficult to read.

The process of "smoothing out" the oscillation of the pointer is known as DAMPING. There are two basic techniques used to damp the pointer of a d’Arsonval meter movement.

The first method of damping comes from the d’Arsonval meter movement itself. In the d’Arsonval meter movement, current through the coil causes the coil to move in the magnetic field of the permanent magnet. This movement of the coil (conductor) through a magnetic field causes a current to be induced in the coil opposite to the current that caused the movement of the coil. This induced current will act to damp oscillations. In addition to this method of damping, which comes from the movement itself, most meters use a second method of damping.

p. 27

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-18 UNCLASSIFIED The second method of damping used in most meter movements is an airtight chamber containing a vane (like a windmill vane) attached to the coil (fig.1-14).

As the coil moves, the vane moves within the airtight chamber. The action of the vane against the air in the chamber opposes the coil movement and damps the oscillations.

Q13. How can a d’Arsonval meter movement be adapted for use as an ac meter? Q14. What is damping? Q15. What are two methods used to damp a meter movement?

Figure 1-14 A typical meter damping system

p. 28

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-19 UNCLASSIFIED Q16. What value does a meter movement react to (actually measure) when measuring ac? Q17. What value is indicated on the scale of an ac meter? An additional advantage of damping a meter movement is that the damping systems will act to slow down the coil and help keep the pointer from overshooting its rest position when the current through the meter is removed.

1.3.6 Indicating Alternating Current Another problem encountered in measuring ac is that the meter movement reacts to the average value of the ac. The value used when working with ac is the effective value (rms value). Therefore, a different scale is used on an ac meter. The scale is marked with the effective value, even though it is the average value to which the meter is reacting. That is why an ac meter will give an incorrect reading if used to measure dc.

1.3.7 Other Meter Movements The d’Arsonval meter movement (permanent-magnet moving-coil) is only one type of meter movement. Other types of meter movements can be used for either ac or dc measurement without the use of a rectifier.

When galvanometers were mentioned earlier in this topic, it was stated that they could be either electromagnetic or electrodynamic. Electrodynamic meter movements will be discussed at this point.

p. 29

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-20 UNCLASSIFIED 1.3.8 Electrodynamic Meter Movement An electrodynamic movement uses the same basic operating principle as the basic moving-coil meter movement, except that the permanent magnet is replaced by fixed coils (fig. 1-15). A moving coil, to which the meter pointer is attached, is suspended between two field coils and connected in series with these coils. The three coils (two field coils and the moving coil) are connected in series across the meter terminals so that the same current flows through each.

Current flow in either direction through the three coils causes a magnetic field to exist between the field coils. The current in the moving coil causes it to act as a magnet and exert a turning force against a spring. If the current is reversed, the field polarity and the polarity of the moving coil reverse at the same time, and the turning force continues in the original direction. Since reversing the current direction does not reverse the turning force, this type of meter can be used to measure both ac and dc if the scale is changed. While some voltmeters and ammeters use the electrodynamic principle of operation, the most important application is in the wattmeter. The wattmeter, along with the voltmeter and the ammeter, will be discussed later in this topic.

Figure 1-15 Electrodynamic meter movement

p. 30

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-21 UNCLASSIFIED 1.3.9 Moving-Vane Meter Movements The moving-vane meter movement (sometimes called the moving-iron movement) is the most commonly used movement for ac meters. The moving-vane meter operates on the principle of magnetic repulsion between like poles (fig.1-16). The current to be measured flows through a coil, producing a magnetic field which is proportional to the strength of the current. Suspended in this field are two iron vanes. One is in a fixed position, the other, attached to the meter pointer, is movable. The magnetic field magnetizes these iron vanes with the same polarity regardless of the direction of current flow in the coil. Since like poles repel, the movable vane pulls away from the fixed vane, moving the meter pointer. This motion exerts a turning force against the spring. The distance the vane will move against the force of the spring depends on the strength of the magnetic field, which in turn depends on the coil current.

These meters are generally used at 60-hertz ac, but may be used at other ac frequencies. By changing the meter scale to indicate dc values rather than ac rms values, moving-vane meters will measure dc current and dc voltage. This is not recommended due to the residual magnetism left in the vanes, which will result in an error in the instrument.

Figure 1-16 Moving-vane meter movement

p. 31

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-22 UNCLASSIFIED One of the major disadvantages of this type of meter movement occurs due to the high reluctance of the magnetic circuit. This causes the meter to require much more power than the D’Arsonval meter to produce a full scale deflection, thereby reducing the meters sensitivity.

1.3.10 Hot-Wire and Thermocouple Meter Movements Hot-wire and thermocouple meter movements both use the heating effect of current flowing through a resistance to cause meter deflection. Each uses this effect in a different manner. Since their operation depends only on the heating effect of current flow, they may be used to measure both direct current and alternating current of any frequency on a single scale.

The hot-wire meter movement deflection depends on the expansion of a high-resistance wire caused by the heating effect of the wire itself as current flows through it. (See fig. 1- 17.) A resistance wire is stretched taut between the two meter terminals, with a thread attached at a right angle to the center of the wire. A spring connected to the opposite end of the thread exerts a constant tension on the resistance wire. Current flow heats the wire, causing it to expand. This motion is transferred to the meter pointer through the thread and a pivot.

Figure 1-17 Hot-wire meter movement

p. 32

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-23 UNCLASSIFIED The thermocouple meter consists of a resistance wire across the meter terminals, which heats in proportion to the amount of current. (See fig. 1-18.) Attached to this wire is a small thermocouple junction of two unlike metal wires, which connect across a very sensitive dc meter movement (usually a d’Arsonval meter movement). As the current being measured heats the heating resistor, a small current (through the thermocouple wires and the meter movement) is generated by the thermocouple junction. The current being measured flows through only the resistance wire, not through the meter movement itself. The pointer turns in proportion to the amount of heat generated by the resistance wire.

Q18. List three meter movements that can measure either ac or dc without the use of a rectifier. Q19. What electrical property is used by all the meter movements discussed so far?

Figure 1-18 A thermocouple meter

p. 33

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-24 UNCLASSIFIED 1.3.11 Ammeters An ammeter is a device that measures current. Since all meter movements have resistance, a resistor will be used to represent a meter in the following explanations. Direct current circuits will be used for simplicity of explanation.

1.3.11.1 Ammeter Connected in Series In figure 1-19(A), R 1 and R2 are in series. The total circuit resistance is R2 + R2 and total circuit current flows through both resistors. In figure 1-19(B), R1 and R2 are in parallel. The total circuit resistance is

1 1 R1 + 1 R2

and total circuit current does not flow through either resistor.

Figure 1-19 A series and a parallel circuit

p. 34

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-25 UNCLASSIFIED If R1 represents an ammeter, the only way in which total circuit current will flow through the meter (and thus be measured) is to have the meter (R1) in series with the circuit load (R2), as shown in figure 1-19(A).

In complex electrical circuits, you are not always concerned with total circuit current. You may be interested in the current through a particular component or group of components. In any case, an ammeter is always connected in series with the circuit you wish to test. Figure 1-20 shows various circuit arrangements with the ammeter(s) properly connected for measuring current in various portions of the circuit.

Connecting an ammeter in parallel would give you not only an incorrect measurement, it would also damage the ammeter, because too much current would pass through the meter.

Figure 1-20 Proper ammeter connections

p. 35

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-26 UNCLASSIFIED 1.3.11.2 Effect on Circuit Being Measured The meter affects the circuit resistance and the circuit current. If R1 is removed from the circuit in figure 1-19(A), the total circuit resistance is R2. Circuit current

(I)equals E R2

with the meter (R1) in the circuit, circuit resistance is R1 + R2 and circuit current

(I) E R2 + R2

The smaller the resistance of the meter (R 1 ), the less it will affect the circuit being measured. (R1 represents the total resistance of the meter; not just the resistance of the meter movement.)

1.3.11.3 Ammeter Sensitivity Ammeter sensitivity is the amount of current necessary to cause full scale deflection (maximum reading) of the ammeter. The smaller the amount of current, the more "sensitive" the ammeter. For example, an ammeter with a maximum current reading of 1 milliampere would have a sensitivity of 1 milliampere, and be more sensitive than an ammeter with a maximum reading of 1 ampere and a sensitivity of 1 ampere. Sensitivity can be given for a meter movement, but the term "ammeter sensitivity" usually refers to the entire ammeter and not just the meter movement. An ammeter consists of more than just the meter movement.

p. 36

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-27 UNCLASSIFIED 1.3.11.4 Ammeter Ranges If you have a meter movement with a sensitivity of 1 milliampere, you can connect it in series with a circuit and measure currents up to 1 milliampere. But what do you do to measure currents over 1 milliampere?

To answer this question, look at figure 1-21. In figure 1-21(A), 10 volts are applied to two resistors in parallel. R 1 is a 10-ohm resistor and R2 is a 1.11-ohm resistor. Since voltage in parallel branches is equal-

IR1 = 10V 10Ω = 1A

IR2 = 10V 1.11Ω = 9A

Figure 1-21 Current in a parallel circuit

p. 37

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-28 UNCLASSIFIED In figure 1-21(B), the voltage is increased to 100 volts. Now,

IR1 = 100V 10Ω = 10A

IR2 = 100V 1.11Ω = 90A

In figure 1-21(C), the voltage is reduced from 100 volts to 50 volts. In this case,

IR1 = 50V 10Ω = 5A

IR2 = 50V 1.11Ω = 45A

Notice that the relationship (ratio) of I R1 and IR2 remains the same. IR2 is nine times greater than IR1 and IR1 has one-tenth of the total current.

If R 1 is replaced by a meter movement that has 10 ohms of resistance and a sensitivity of 10 amperes, the reading of the meter will represent one-tenth of the current in the circuit and R2 will carry nine-tenths of the current. R2 is a SHUNT resistor because it diverts, or shunts, a portion of the current from the meter movement (R1). By this method, a 10- ampere meter movement will measure current up to 100 amperes. By adding a second scale to the face of the meter, the current can be read directly.

By adding several shunt resistors in the meter case, with a switch to select the desired resistor, the ammeter will be capable of measuring several different maximum current readings or ranges.

p. 38

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-29 UNCLASSIFIED Most meter movements in use today have sensitivities of from 5 microamperes to 1 milliampere. Figure 1-22 shows the circuit of meter switched to higher ranges, the shunt an ammeter that uses a meter movement with a sensitivity of 100 microamperes and shunt resistors. This ammeter has five ranges (100 microamperes; 1, 10, and 100 milliamperes; 1 ampere) selected by a switch.

By adding several shunt resistors in the meter case, with a switch to select the desired resistor, the ammeter will be capable of measuring several different maximum current readings or ranges.

Most meter movements in use today have sensitivities of from 5 microamperes to 1 milliampere. Figure 1-22 shows the circuit of meter switched to higher ranges, the shunt an ammeter that uses a meter movement with a sensitivity of 100 microamperes and shunt resistors. This ammeter has five ranges (100 microamperes; 1, 10, and 100 milliamperes; 1 ampere) selected by a switch.

Figure 1-22 An ammeter with internal shunt resistors

p. 39

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-30 UNCLASSIFIED With the switch in the 100 microampere position, all the current being measured will go through the meter movement. None of the current will go through any of the shunt resistors. If the ammeter is switched to the 1 milliampere position, the current being measured will have parallel paths of the meter movement and all the shunt resistors (R 1 , R2, R3, and R4). Now, only a portion of the current will go through the meter movement and the rest of the current will go through the shunt resistors. When the meter is switched to the 10-milliampere position (as shown in fig. 1-22), only resistors R 1, R2, and R3 shunt the meter. Since the resistance of the shunting resistance is less than with R4 in the circuit (as was the case in the 1-milliampere position), more current will go through the shunt resistors and less current will go through the meter movement. As the resistance decreases and more current goes through the shunt resistors. As long as the current to be measured does not exceed the range selected, the meter movement will never have more than 100 microamperes of current through it.

Shunt resistors are made with close tolerances. That means if a shunt resistor is selected with a resistance of .01 ohms (as R 1 in fig. 1-22), the actual resistance of that shunt resistor will not vary from that value by more than 1 percent. Since a shunt resistor is used to protect a meter movement and to allow accurate measurement, it is important that the resistance of the shunt resistor is known very accurately.

Figure 1-22 represents an ammeter with internal shunts. The shunt resistors are inside the meter case and selected by a switch. For limited current ranges (below 50 amperes), internal shunts are most often employed.

For higher current ranges (above 50 amperes) ammeters that use external shunts are used. The external shunt resistor serves the same purpose as the internal shunt resistor. The external shunt is connected in series with the circuit to be measured and in parallel with the ammeter. This shunts (bypasses) the ammeter so only a portion of the current goes through the meter. Each external shunt will be marked with the maximum current value that the ammeter will measure when that shunt is used. Figure 1-23 shows an ammeter that is designed to use external shunts and a d’Arsonval meter movement. Figure 1-23(A) shows the internal construction of the meter and the way in which the external shunt is connected to the meter and to the circuit being measured. Figure 1-23(C) shows some typical external shunts.

p. 40

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-31 UNCLASSIFIED

A shunt resistor is nothing more than a resistor in parallel with the meter movement. To measure high currents, very small resistance shunts are used so the majority of the current will go through the shunt. Since the total resistance of a parallel circuit (the meter movement and shunt resistor) is always less than the resistance of the smallest resistor, as an ammeter’s range is increased, its resistance decreases. This is important because the load resistance of high-current circuits is smaller than the load resistance of low-current circuits. To obtain accurate measurements, it is necessary that the ammeter resistance is much less than the load resistance, since the ammeter is connected in series with the load.

Figure 1-23 An ammeter employing the d’Arsonval principle and external shunts

p. 41

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-32 UNCLASSIFIED Q20. What electrical property does an ammeter measure? Q21. How is an ammeter connected to the circuit under test? Q22. How does an ammeter affect the circuit being measured? Q23. How is the ammeter’s effect on the circuit being measured kept to a minimum? Q24. What is ammeter sensitivity? Q25. What is used to allow an ammeter to measure different ranges?

p. 42

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-33 UNCLASSIFIED 1.3.11.4.1 Range Selection Part of the correct use of an ammeter is the proper use of the range selection switch. If the current to be measured is larger than the scale of the meter selected, the meter movement will have excessive current and will be damaged. Therefore, it is important to always start with the highest range when you use an ammeter. If the current can be measured on several ranges, use the range that results in a reading near the middle of the scale. Figure 1-24 illustrates these points.

Figure 1-24(A) shows the initial reading of a circuit. The highest range (250 milliamperes) has been selected and the meter indication is very small. It would be difficult to properly interpret this reading with any degree of accuracy. Figure 1-24(B) shows the second reading, with the next largest range (50 milliamperes). The meter deflection is a little greater. It is possible to interpret this reading as 5 milliamperes. Since this approximation of the current is less than the next range, the meter is switched as shown in figure 1-24(C). The range of the meter is now 10 milliamperes and it is possible to read the meter indication of 5 milliamperes with the greatest degree of accuracy. Since the current indicated is equal to (or greater than) the next range of the ammeter (5 milliamperes), the meter should NOT be switched to the next range.

Figure 1-24 Reading an ammeter at various ranges

p. 43

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-34 UNCLASSIFIED 1.3.11.5 Ammeter Safety Precautions When you use an ammeter, certain precautions must be observed to prevent injury to yourself or others and to prevent damage to the ammeter or the equipment on which you are working. The following list contains the MINIMUM precautions to observe when using an ammeter.

• Ammeters must always be connected in series with the circuit under test. • Always start with the highest range of an ammeter. • Deenergize and discharge the circuit completely before you connect or disconnect the ammeter. • In dc ammeters, observe the proper circuit polarity to prevent the meter from being damaged. • Never use a dc ammeter to measure ac. • Observe the general safety precautions of electrical and electronic devices.

Q26. Why should you use the highest range of an ammeter for the initial measurement? Q27. What range of an ammeter is selected for the final measurement? Q28. List the six safety precautions for the use of ammeters. Q29. Why will an ammeter be damaged if connected in parallel with the circuit to be measured? 1.3.12 Voltmeters All the meter movements discussed so far react to current, and you have been shown how ammeters are constructed from those meter movements. It is often necessary to measure circuit properties other than current. Voltage measurement, for example, is accomplished with a VOLTMETER.

p. 44

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-35 UNCLASSIFIED 1.3.12.1 Voltmeters Connected in Parallel While ammeters are always connected in series, voltmeters are always connected in parallel. Figure 1-25 (and the following figures) use resistors to represent the voltmeter movement. Since a meter movement can be considered as a resistor, the concepts illustrated are true for voltmeters as well as resistors. For simplicity, dc circuits are shown, but the principles apply to both ac and dc voltmeters.

Figure 1-25 Current and voltage in series and parallel circuits

p. 45

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-36 UNCLASSIFIED Figure 1-25(A) shows two resistors connected in parallel. Notice that the voltage across both resistors is equal. In figure 1-25(B) the same resistors are connected in series. In this case, the voltage across the resistors is not equal. If R1 represents a voltmeter, the only way in which it can be connected to measure the voltage of R2 is in parallel with R2, as in figure 1-25(A).

1.3.12.2 Loading Effect A voltmeter has an effect on the circuit being measured. This is called LOADING the circuit. Figure 1-26 illustrates the loading effect and the way in which the loading effect is kept to a minimum.

Figure 1-26 The loading effect

p. 46

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-37 UNCLASSIFIED In figure 1-26(A), a series circuit is shown with R1 equaling 15 ohms and R2 equaling 10 ohms. The voltage across R2 (ER2) equals 10 volts. If a meter (represented by R3) with a resistance of 10 ohms is connected in parallel with R2, as in figure 1-26(B), the combined resistance of R2 and R3 (Rn) is equal to 5 ohms. The voltage across R2 and R3 is now 6.25 volts, and that is what the meter will indicate. Notice that the voltage across R1 and the circuit current have both increased. The addition of the meter (R3) has loaded the circuit.

In figure 1-26(C), the low-resistance meter (R3) is replaced by a higher resistance meter (R 4) with a resistance of 10 kilohms. The combined resistance of R2 and R4 (Rn) is equal to 9.99 ohms. The voltage across R2 and R 4 is now 9.99 volts, the value that will be indicated on the meter. This is much closer to the voltage across R2, with no meter (R3 or R4) in the circuit. Notice that the voltage across R, and the circuit current in figure 1-26(C) are much closer to the values in 1-26(A). The current (IR4) through the meter (R4) in figure 1-26(C) is also very small compared to the current (IR2) through R 2. In figure 1- 26(C) the meter (R4) has much less effect on the circuit and does not load the circuit as much. Therefore, a voltmeter should have a high resistance compared to the circuit being measured, to minimize the loading effect.

Q30. What electrical quantity is measured by a voltmeter? Q31. How is a voltmeter connected to the circuit to be measured? Q32. What is the loading effect of a voltmeter? Q33. How is the loading effect of a voltmeter kept to a minimum?

p. 47

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-38 UNCLASSIFIED 1.3.12.3 Making a Voltmeter from a Current Sensitive Meter Movement The meter movements discussed earlier in this chapter have all reacted to current. Various ways have been shown in which these movements can be used in ammeters. If the current and resistance are known, the voltage can be calculated by the formula E = IR. A meter movement has a known resistance, so as the movement reacts to the current, the voltage can be indicated on the scale of the meter.

In figure 1-27(A), a voltmeter (represented by R 2) connected across a 10-ohm resistor with 10 volts applied. The current through the voltmeter (R2) is .1 milliamperes. In figure 1-27(B), the voltage is increased to 100 volts. Now, the current through the voltmeter (R2) is 1 milliampere. The voltage has increased by a factor of 10 and so has the current. This illustrates that the current through the meter is proportional to the voltage being measured.

Figure 1-27 Current and voltage in parallel circuit

p. 48

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-39 UNCLASSIFIED 1.3.12.4 Sensitivity of Voltmeters Voltmeter sensitivity is expressed in ohms per volt (Ω/V). It is the resistance of the voltmeter at the full-scale reading in volts. Since the voltmeter’s resistance does not change with the position of the pointer, the total resistance of the meter is the sensitivity multiplied by the full-scale voltage reading. The higher the sensitivity of a voltmeter, the higher the voltmeter’s resistance. Since high resistance voltmeters have less loading effect on circuits, a high-sensitivity meter will provide a more accurate voltage measurement.

To determine the sensitivity of a meter movement, you need only to divide 1 by the amount of current needed to cause full-scale deflection of the meter movement. The manufacturer usually marks meter movements with the amount of current needed for full- scale deflection and the resistance of the meter. With these figures, you can calculate the sensitivity

( 1 full − scale current )

and the full-scale voltage reading full-scale current (full-scale current x resistance).

For example, if a meter has a full-scale current of 50μA and a resistance of 960Ω the sensitivity could be calculated as:

Sensitivity = 1 full − scale current

Sensitivity = 1 50µA

Sensitivity = 20kΩ/volt

The full-scale voltage reading would be calculated as:

Full-scale voltage reading = full-scale current × resistance

Full-scale voltage reading = 50μA x 960Ω

Full-scale voltage reading = 48mV

p. 49

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-40 UNCLASSIFIED 1.3.12.5 Ranges Table 1-1 shows the figures for most meter movements in use today.

Table 1-1 Meter Movement Characteristics CURRENT TO DEFLECT FULL SCALE RESISTANCE SENSITIVITY VOLTAGE FULL SCALE 1mA 100Ω 1kΩ/volt .1V 50μA 960Ω 20kΩ/volt .048V 5μA 5750Ω 200kΩ/volt .029V

Notice that the meter movements shown in table 1-1 will indicate .029 volts to .I volt at full scale, and the sensitivity ranges from 1000 ohms per volt to 200,000 ohms per volt. The higher sensitivity meters indicate smaller amounts of voltage. Since most voltage measurements involve voltage larger than .1 volt, a method must be used to extend the voltage reading.

p. 50

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-41 UNCLASSIFIED Figure 1-28 illustrates the method of increasing the voltage range of a voltmeter.

In figure 1-28(A), a voltmeter with a range of 10 volts and a resistance of 1 kilohm (R 2) is connected in parallel to resistor R1. The meter has .01 ampere of current (full-scale deflection) and indicates 10 volts. In figure 1-28(B), the voltage has been increased to 100 volts. This is more than the meter can measure. A 9 kilohm resistor (R3) is connected in series with the meter (R2). The meter (R2) now has .01 ampere of current (full-scale deflection). But since R3 has increased the voltage capability of the meter, the meter indicates 100 volts. R3 has changed the range of the meter.

Figure 1-28 A voltmeter and a range resistor

p. 51

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-42 UNCLASSIFIED Voltmeters can be constructed with several ranges by the use of a switch and internal resistors. Figure 1-29 shows a voltmeter with a meter movement of 100 ohms and 1 milliampere full-scale deflection with 5 ranges of voltage through the use of a switch. In this way a voltmeter can be used to measure several different ranges of voltage.

The current through the meter movement is determined by the voltage being measured. If the voltage measured is higher than the range of the voltmeter, excess current will flow through the meter movement and the meter will be damaged. Therefore, you should always start with the highest range of a voltmeter and switch the ranges until a reading is obtained near the center of the scale. Figure 1-30 illustrates these points.

Figure 1-29 A voltmeter with internal range resistors

p. 52

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-43 UNCLASSIFIED

In figure 1-30(A) the meter is in the 1000-volt range. The pointer is barely above the 0 position. It is not possible to accurately read this voltage. In figure 1-30(B) the meter is switched to the 250 volt range. From the pointer position it is possible to approximate the voltage as 20 volts. Since this is well below the next range, the meter is switched, as in figure 1-30(C). With the meter in the 50-volt range, it is possible to read the voltage as 22 volts. Since this is more than the next range of the meter (10 volts), the meter would not be switched to the next (lower) scale.

Q34. How is it possible to use a current sensitive meter movement to measure voltage? Q35. What is voltmeter sensitivity? Q36. What method is used to allow a voltmeter to have several ranges?

Figure 1-30 Reading a voltmeter at various ranges

p. 53

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-44 UNCLASSIFIED Q37. Why should you always use the highest range when connecting a voltmeter to a circuit? 1.3.12.6 Electrostatic Meter Movement The final meter movement covered in this chapter is the ELECTROSTATIC METER MOVEMENT. The other meter movements you have studied all react to current , the electrostatic meter movement reacts to voltage.

The mechanism is based on the repulsion of like charges on the plates of a capacitor. The electrostatic meter movement is actually a large variable capacitor in which one set of plates is allowed to move. The movement of the plates is opposed by a spring attached to the plates. A pointer that indicates the value of the voltage is attached to these movable plates. As the voltage increases, the plates develop more torque. To develop sufficient torque, the plates must be large and closely spaced. A very high voltage is necessary to provide movement; therefore, electrostatic voltmeters are used only for HIGH VOLTAGE measurement.

1.3.12.7 Voltmeter Safety Precautions Just as with ammeters, voltmeters require safety precautions to prevent injury to personnel and damage to the voltmeter or equipment. The following is a list of the MINIMUM safety precautions for using a voltmeter.

• Always connect voltmeters in parallel. • Always start with the highest range of a voltmeter. • Deenergize and discharge the circuit completely before connecting or disconnecting the voltmeter. • In dc voltmeters, observe the proper circuit polarity to prevent damage to the meter. • Never use a dc voltmeter to measure ac voltage. • Observe the general safety precautions of electrical and electronic devices.

Q38. What type of meter movement reacts to voltage rather than current? Q39. What is the only use for the voltage sensitive meter movement? Q40. List the six safety precautions for the use of voltmeters.

p. 54

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-45 UNCLASSIFIED 1.3.13 OHMMETERS The two instruments most commonly used to check the continuity (a complete circuit), or to measure the resistance of a circuit or circuit element, are the OHMMETER and the MEGGER (megohm meter). The ohmmeter is widely used to measure resistance and check the continuity of electrical circuits and devices. Its range usually extends to only a few megohms. The megger is widely used for measuring insulation resistance, such as between a wire and the outer surface of the insulation, and insulation resistance of cables and insulators. The range of a megger may extend to more than 1,000 megohms.

The ohmmeter consists of a dc ammeter, with a few added features. The added features are:

1. A dc source of potential (usually a 3-volt battery)

2. One or more resistors (one of which is variable)

3. A simple ohmmeter circuit is shown in figure 1-31.

Figure 1-31 A simple ohmmeter circuit

p. 55

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-46 UNCLASSIFIED The ohmmeter’s pointer deflection is controlled by the amount of battery current passing through the moving coil. Before measuring the resistance of an unknown resistor or electrical circuit, the test leads of the ohmmeter are first shorted together, as shown in figure 1-31. With the leads shorted, the meter is calibrated for proper operation on the selected range. While the leads are shorted, meter current is maximum and the pointer deflects a maximum amount, somewhere near the zero position on the ohms scale. Because of this current through the meter with the leads shorted, it is necessary to remove the test leads when you are finished using the ohmmeter. If the leads were left connected, they could come in contact with each other and discharge the ohmmeter battery. When the variable resistor (rheostat) is adjusted properly, with the leads shorted, the pointer of the meter will come to rest exactly on the zero position. This indicates ZERO RESISTANCE between the test leads, which, in fact, are shorted together. The zero reading of a series-type ohmmeter is on the right-hand side of the scale, where as the zero reading for an ammeter or a voltmeter is generally to the left-hand side of the scale. (There is another type of ohmmeter which is discussed a little later on in this chapter.) When the test leads of an ohmmeter are separated, the pointer of the meter will return to the left side of the scale. The interruption of current and the spring tension act on the movable coil assembly, moving the pointer to the left side (∞) of the scale.

1.3.13.1 Using the Ohmmeter After the ohmmeter is adjusted for zero reading, it is ready to be connected in a circuit to measure resistance. A typical circuit and ohmmeter arrangement is shown in figure 1-32.

The power switch of the circuit to be measured should always be in the OFF position. This prevents the source voltage of the circuit from being applied across the meter, which could cause damage to the meter movement.

p. 56

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-47 UNCLASSIFIED The test leads of the ohmmeter are connected in series with the circuit to be measured (fig. 1-32). This causes the current produced by the 3-volt battery of the meter to flow through the circuit being tested. Assume that the meter test leads are connected at points a and b of figure 1-32. The amount of current that flows through the meter coil will depend on the total resistance of resistors R1 and R2, and the resistance of the meter. Since the meter has been pre-adjusted (zeroed), the amount of coil movement now depends solely on the resistance of R1and R2. The inclusion of R1 and R2 raises the total series resistance, decreasing the current, and thus decreasing the pointer deflection. The pointer will now come to rest at a scale figure indicating the combined resistance of R1 and R2. If R1 or R2, or both, were replaced with a resistor(s) having a larger value, the current flow in the moving coil of the meter would be decreased further. The deflection would also be further decreased, and the scale indication would read a still higher circuit resistance. Movement of the moving coil is proportional to the amount of current flow.

Figure 1-32 Measuring circuit resistance with an ohmmeter

p. 57

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-48 UNCLASSIFIED 1.3.13.2 Ohmmeter Ranges The amount of circuit resistance to be measured may vary over a wide range. In some cases it may be only a few ohms, and in others it may be as great as 1,000,000 ohms (1 megohm). To enable the meter to indicate any value being measured, with the least error, scale multiplication features are used in most ohmmeters. For example, a typical meter will have four test lead jacks-COMMON, R × 1, R × 10, and R × 100. The jack marked COMMON is connected internally through the battery to one side of the moving coil of the ohmmeter. The jacks marked R × 1, R × 10, and R × 100 are connected to three different size resistors located within the ohmmeter. This is shown in figure 1-33.

Some ohmmeters are equipped with a selector switch for selecting the multiplication scale desired, so only two test lead jacks are necessary. Other meters have a separate jack for each range, as shown in figure 1-33. The range to be used in measuring any particular unknown resistance (R x in figure 1-33) depends on the approximate value of the unknown resistance. For instance, assume the ohmmeter in figure 1-33 is calibrated in divisions from 0 to 1,000. If Rx is greater than 1,000 ohms, and the R x 1 range is being used, the ohmmeter cannot measure it.

Figure 1-33 An ohmmeter with multiplication jacks

p. 58

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-49 UNCLASSIFIED This occurs because the combined series resistance of resistor R × 1 and Rx is too great to allow sufficient battery current to flow to deflect the pointer away from infinity (∞). (Infinity is a quantity larger than the largest quantity you can measure.) The test lead would have to be plugged into the next range, R × 10. With this done, assume the pointer deflects to indicate 375 ohms. This would indicate that Rx has 375 ohms × 10, or 3,750 ohms resistance. The change of range caused the deflection because resistor R × 10 has about 1/10 the resistance of resistor R × 1. Thus, selecting the smaller series resistance permitted a battery current of sufficient amount to cause a useful pointer deflection. If the R × 100 range were used to measure the same 3,750-ohm resistor, the pointer would deflect still further, to the 37.5-ohm position. This increased deflection would occur because resistor R × 100 has about 1/10 the resistance of resistor R × 10.

The foregoing circuit arrangement allows the same amount of current to flow through the meter’s moving coil whether the meter measures 10,000 ohms on the R × 10 scale, or 100,000 ohms on the R × 100 scale.

It always takes the same amount of current to deflect the pointer to a certain position on the scale (midscale position for example), regardless of the multiplication factor being used. Since the multiplier resistors are of different values, it is necessary to ALWAYS "zero" adjust the meter for each multiplication fact or selected.

You should select the multiplication factor (range) that will result in the pointer coming to rest as near as possible to the midpoint of the scale . This enables you to read the resistance more accurately, because the scale readings are more easily interpreted at or near midpoint.

Q41. What electrical quantity is measured by an ohmmeter? Q42. What other measurement can an ohmmeter make? Q43. How is a series-type ohmmeter connected to the circuit being measured? Q44. What is used to provide the ohmmeter with several ranges? Q45. What area of an ohmmeter scale should be used when measuring circuits?

p. 59

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-50 UNCLASSIFIED 1.3.13.3 Shunt Ohmmeter The ohmmeter described to this point is known as a series ohmmeter, because the resistance to be measured is in series with the internal resistors and the meter movement of the ohmmeter. Another type of ohmmeter is the SHUNT OHMMETER. In the shunt ohmmeter, the resistance to be measured shunts (is in parallel with) the meter movement of the ohmmeter. The most obvious way to tell the difference between the series and shunt ohmmeters is by the scale of the meter. Figure 1-34 shows the scale of a series ohmmeter and the scale of a shunt ohmmeter.

Figure 1-34 Series and shunt ohmmeter scales

p. 60

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-51 UNCLASSIFIED Figure 1-34(A) is the scale of a series ohmmeter. Notice "0" is on the right and "∞" is on the left. Figure 1-34(B) is the scale of a shunt ohmmeter. In the shunt ohmmeter "∞" is on the right and "0" is on the left. A shunt ohmmeter circuit is shown in figure 1-35.

In figure 1-35, R1 is a rheostat used to adjust the ∞ reading of the meter (full-scale deflection). R2, R3, and R4 are used to provide the R × 1, R × 10, and R × 100 ranges. Points A and B represent the meter leads. With no resistance connected between points A and B the meter has full-scale current and indicates ∞. If a resistance is connected between points A and B, it shunts some of the current from the meter movement and the meter movement reacts to this lower current. Since the scale of the meter is marked in ohms, the resistance of the shunting resistor (between points A and B) is indicated. Notice that the switch has an OFF position, as well as positions for R × 1, R × 10, and R × 100. This is provided to stop current flow and prevents the battery from being discharged while the meter is not being used.

The shunt ohmmeter is connected to the circuit to be measured in the same way the series ohmmeter is connected. The only difference is that on the shunt ohmmeter the ∞ reading is adjusted, while on the series ohmmeter the 0 reading is adjusted. Shunt ohmmeters are not commonly used because they are limited generally to measuring resistances from 5 ohms to 400 ohms. If you use a shunt ohmmeter, be certain to switch it to the OFF position when you are finished using it.

Figure 1-35 A shunt ohmmeter with internal range resistors

p. 61

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-52 UNCLASSIFIED Q46. What are the two types of ohmmeters? Q47. What is the most obvious difference between the two types of ohmmeters? Q48. List the four safety precautions observed when using ohmmeters. 1.3.13.4 Ohmmeter Safety Precautions The following safety precautions and operating procedures for ohmmeters are the MINIMUM necessary to prevent injury and damage.

• Be certain the circuit is deenergized and discharged before connecting an ohmmeter. • Do not apply power to a circuit while measuring resistance. • When you are finished using an ohmmeter, switch it to the OFF position if one is provided and remove the leads from the meter. • Always adjust the ohmmeter for 0 (or ∞ in shunt ohmmeter) after you change ranges before making the resistance measurement.

1.3.14 Megohmmeter An ordinary ohmmeter cannot be used for measuring resistance of multimillions of ohms, such as in conductor insulation. To adequately test for insulation break down, it is necessary to use a much higher potential than is furnished by the battery of an ohmmeter. This potential is placed between the conductor and the outside surface of the insulation.

An instrument called a MEGOHMMETER (MEGGER) is used for these tests. The megger (fig. 1-36) is a portable instrument consisting of two primary elements: (1) a hand-driven dc generator, G, which supplies the high voltage for making the measurement, and (2) the instrument portion, which indicates the value of the resistance being measured. The instrument portion is of the opposed-coil type, as shown in figure 1-36(A). Coils a and b are mounted on the movable member c with a fixed relationship to each other, and are free to turn as a unit in a magnetic field. Coil b tends to move the pointer counterclockwise, and coil a tends to move the pointer clockwise.

p. 62

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-53 UNCLASSIFIED

Coil a is connected in series with R 3 and the unknown resistance, Rx, to be measured. The combination of coil, R3, and Rx forms a direct series path between the positive (+) and negative (−) brushes of the dc generator. Coil b is connected in series with R2 and this combination is also connected across the generator. There are no restraining springs on the movable member of the instrument portion of the megger. Therefore, when the generator is not operated, the pointer floats freely and may come to rest at any position on the scale.

The guard ring intercepts leakage current. Any leakage currents intercepted are shunted to the negative side of the generator. They do not flow through coil a; therefore, they do not affect the meter reading.

Figure 1-36 A megger internal circuit

p. 63

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-54 UNCLASSIFIED If the test leads are open-circuited, no current flows in coil a. However, current flows internally through coil b, and deflects the pointer to infinity, which indicates a resistance too large to measure. When a resistance such as Rx is connected between the test leads, current also flows in coil a, tending to move the pointer clockwise. At the same time, coil b still tends to move the pointer counterclockwise. Therefore, the moving element, composed of both coils and the pointer, comes to rest in a position at which the two forces are balanced. This position depends upon the value of the external resistance, which controls the relative amount of current in coil a. Because changes in voltage affect both coil a and coil b in the same proportion, the position of the moving system is independent of the voltage. If the test leads are short-circuited, the pointer rests at zero because the current in coil a is relatively large. The instrument is not damaged under these circumstances because the current is limited by R3.

The external view of one type of megger is shown in figure 1-36(B).

Navy meggers are usually rated at 500 volts. To avoid excessive test voltages, most meggers are equipped with friction clutches. When the generator is cranked faster than its rated speed, the clutch slips and the generator speed and output voltage are not permitted to exceed their rated values. When extremely high resistances-for example, 10,000 megohms or more are to be measured, a high voltage is needed to cause sufficient current flow to actuate the meter movement. For extended ranges, a 1,000-volt generator is available.

When a megger is used, the generator voltage is present on the test leads. This voltage could be hazardous to you or to the equipment you are checking. Therefore, NEVER TOUCH THE TEST LEADS WHILE THE MEGGER IS BEING USED and isolate the item you are checking from the equipment before using the megger.

1.3.14.1 Using the Megger To use a megger to check wiring insulation, connect one test lead to the insulation and the other test lead to the conductor, after isolating the wiring from the equipment. Turn the hand crank until the slip clutch just begins to slip and note the meter reading. Normal insulations should read infinity. Any small resistance reading indicates the insulation is breaking down.

p. 64

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-55 UNCLASSIFIED 1.3.14.2 Megger Safety Precautions When you use a megger, you could be injured or damage equipment you are working on if the following MINIMUM safety precautions are not observed.

• Use meggers on high-resistance measurements only (such as insulation measurements or to check two separate conductors on a cable). • Never touch the test leads while the handle is being cranked. • Deenergize and discharge the circuit completely before connecting a megger. • Disconnect the item being checked from other circuitry, if possible, before using a megger.

Q49. What is the primary use of a megger? Q50. What is the procedure for using a megger to check the insulation of a conductor? Q51. What is a normal indication on a megger when checking insulation? Q52. List the four safety precautions observed when using a megger.

p. 65

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-56 UNCLASSIFIED 1.3.15 Multimeter A MULTIMETER is the most common measuring device used in the Navy. The name multimeter comes from MULTIple METER, and that is exactly what a multimeter is. It is a dc ammeter, a dc voltmeter, an ac voltmeter, and an ohmmeter, all in one package. Figure 1-37 is a picture of a typical multimeter.

Figure 1-37 A typical multimeter

p. 66

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-57 UNCLASSIFIED The multimeter shown in figure 1-37 may look complicated, but it is very easy to use. You have already learned about ammeters, voltmeters, and ohmmeters; the multimeter is simply a combination of these meters.

Most multimeters use a d’Arsonval meter movement and have a built-in rectifier for ac measurement. The lower portion of the meter shown in figure 1-37 contains the function switches and jacks (for the meter leads).

The use of the jacks will be discussed first. The COMMON or -jack is used in all functions is plugged into the COMMON jack. The +jack is used for the second meter lead for any of the functions printed in large letters beside the FUNCTION SWITCH (the large switch in the center). The other jacks have specific functions printed above or below them and are self-explanatory (the output jack is used with the dB scale, which will not be explained in this chapter). To use one of the special function jacks, except +10 amps, one lead is plugged into the COMMON jack, and the FUNCTION SWITCH is positioned to point to the special function (small letters). For example, to measure a very small current (20 microamperes), one meter lead would be plugged into the COMMON jack, the other meter lead would be plugged into the 50A AMPS jack, and the FUNCTION SWITCH would be placed in the 50V/IA AMPS position. To measure currents above 500 milliamperes, the +10A and −10A jacks would be used on the meter with one exception. One meter lead and the FUNCTION SWITCH would be placed in the 10MA/AMPS position.

1.3.15.1 Multimeter Controls As described above, the FUNCTION SWITCH is used to select the function desired; the −DC, +DC, AC switch selects dc or ac (the rectifier), and changes the polarity of the dc functions. To measure resistance, this switch should be in the +DC position.

The ZERO OHMS control is a potentiometer for adjusting the 0 reading on ohmmeter functions. Notice that this is a series ohmmeter. The RESET is a circuit breaker used to protect the meter movement (circuit breakers will be discussed in chapter 2 of this module). Not all multimeters have this protection but most have some sort of protection, such as a fuse. When the multimeter is not in use, it should have the leads disconnected and be switched to the highest voltage scale and AC. These switch positions are the ones most likely to prevent damage if the next person using the meter plugs in the meter leads and connects the meter leads to a circuit without checking the function switch and the dc/ac selector.

p. 67

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-58 UNCLASSIFIED 1.3.15.2 Multimeter Scales The numbers above the uppermost scale in figure 1-38 are used for resistance measurement. If the multimeter was set to the R 1 function, the meter reading × would be approximately 12.7 ohms.

Figure 1-38 A multimeter scale and reading

p. 68

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-59 UNCLASSIFIED The numbers below the uppermost scale are used with the uppermost scale for dc voltage and direct current, and the same numbers are used with the scale just below the numbers for ac voltage and alternating current. Notice the difference in the dc and ac scales. This is because the ac scale must indicate effective ac voltage and current. The third scale from the top and the numbers just below the scale are used for the 2.5-volt ac function only. The lowest scale (labeled DB) will not be discussed. The manufacturer’s technical manual will explain the use of this scale.

The table in figure 1-38 shows how the given needle position should be interpreted with various functions selected.

As you can see, a multimeter is a very versatile measuring device and is much easier to use than several separate meters.

Q53. What is a multimeter? Q54. Why is a multimeter preferred over separate meters? Q55. How is a multimeter changed from a voltage measuring device to a resistance measuring device? Q56. Why is the dc scale on a multimeter different than the ac scale?

p. 69

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-60 UNCLASSIFIED Table 1-2 illustrates an interesting point about multimeters. It was mentioned earlier in this chapter that both voltmeters and ammeters have an effect upon the circuits they measure.

Table 1-2 Multimeter Movements CURRENT TO DEFLECT FULL SCALE METER MOVEMENT RESISTANCE VOLTMETER SENSITIVITY VOLTAGE FULL SCALE SHUNT RESISTOR OVERALL RESISTANCE 1mA 100Ω 1kΩ/volt .1V NA 100Ω 50μA 960Ω 20kΩ/volt .048V 50.5Ω 48Ω 5μA 5750Ω 200kΩ/volt .029V 29.146Ω 28.999Ω

To keep this effect to a minimum, it is necessary that the voltmeter have a high resistance (sensitivity expressed in ohms per volt) and the ammeter have a low resistance compared to the circuit being measured.

Table 1-2 shows the figures associated with three meter movements available for use in multimeters. The last two columns indicate the value of shunt resistance and the overall resistance of the shunt and meter movement necessary to compensate all three movements to an ammeter sensitivity (full-scale current) of 1 milliampere. Notice that as the voltmeter sensitivity increases, the resistance of the ammeter decreases. This shows how a meter movement used in a voltmeter will have a high effective resistance and the same meter movement used in an ammeter will have a low effective resistance because of the shunt resistors.

p. 70

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-61 UNCLASSIFIED 1.3.15.3 Parallax Error Most multimeters (and some other meters) have a mirror built into the scale. Figure 1-39 shows the arrangement of the scale and mirror.

The purpose of the mirror on the scale of a meter is to aid in reducing PARALLAX ERROR. Figure 1-40 will help you understand the idea of parallax.

Figure 1-40(A) shows a section of barbed wire fence as you would see it from one side of the fence. Figure 1-40(B) shows the fence as it would appear if you were to look down the fine of fence posts and were directly in line with the posts. You see only one post because the other posts, being in line, are hidden behind the post you can see. Figure 1- 40(C) shows the way the fence would appear if you moved to the right of the line of posts. Now the fence posts appear to the right of the post closest to you. Figure 1-40(D) shows the line of fence posts as you would see them if you moved to the left of the front post. This apparent change in position of the fence posts is called PARALLAX.

Figure 1-39 A multimeter scale with mirror

p. 71

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-62 UNCLASSIFIED

Parallax can be a problem when you are reading a meter. Since the pointer is slightly above the scale (to allow the pointer to move freely), you must look straight at the pointer to have a correct meter reading. In other words, you must be in line with the pointer and the scale. Figure 1-41 shows the effect of parallax error.

Figure 1-40 Parallax illustration (barbed-wire fence) Figure 1-41 A parallax error in a meter reading

p. 72

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-63 UNCLASSIFIED Figure 1-41 (A) shows a meter viewed correctly. The meter reading is 5 units. Figure 1- 41(B) shows the same meter as it would appear if you were to look at it from the right. The correct reading (5) appears to the right of the pointer because of parallax.

The mirror on the scale of a meter, shown in figure 1-39, helps get rid of parallax error. If there is any parallax, you will be able to see the image of the pointer in the mirror. If you are looking at the meter correctly (no parallax error) you will not be able to see the image of the pointer in the mirror because the image will be directly behind the pointer. Figure 1-42 shows how a mirror added to the meter in figure 1-41 shows parallax error. Figure 1-42(A) is a meter with an indication of 5 units. There is no parallax error in this reading and no image of the pointer is seen in the mirror. Figure 1-42(B) shows the same meter as viewed from the right. The parallax error is shown and the image of the pointer is shown in the mirror.

Figure 1-42 A parallax error on a meter with a mirrored scale

p. 73

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-64 UNCLASSIFIED 1.3.15.4 Multimeter Safety Precautions As with other meters, the incorrect use of a multimeter could cause injury or damage. The following safety precautions are the MINIMUM for using a multimeter.

• Deenergize and discharge the circuit completely before connecting or disconnecting a multimeter. • Never apply power to the circuit while measuring resistance with a multimeter. • Connect the multimeter in series with the circuit for current measurements, and in parallel for voltage measurements. • Be certain the multimeter is switched to ac before attempting to measure ac circuits. • Observe proper dc polarity when measuring dc. • When you are finished with a multimeter, switch it to the OFF position, if available. If there is no OFF position, switch the multimeter to the highest ac voltage position. • Always start with the highest voltage or current range. • Select a final range that allows a reading near the middle of the scale. • Adjust the "0 ohms" reading after changing resistance ranges and before making a resistance measurement. • Be certain to read ac measurements on the ac scale of a multimeter. • Observe the general safety precautions for electrical and electronic devices.

Q57. What is the reason for having a mirror on the scale of a multimeter? Q58. How is the mirror on a multimeter used? Q59. List the 11 safety precautions for multimeters.

p. 74

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-65 UNCLASSIFIED 1.3.16 Other Meters In addition to the ammeter, voltmeter, ohmmeter, and multimeter, you will probably use many other types of measuring devices. Many of those measuring devices (test equipment) are discussed later in this training series. The following brief discussion of a few additional meters will introduce you to some of common measuring devices you will use in working on electrical and electronic circuits.

1.3.16.1 Hook-On Type Voltammeter The hook-on ac ammeter consists essentially of a current transformer with a split core and a rectifier-type instrument connected to the secondary. The primary of the current transformer is the conductor through which the current to be measured flows. The split core permits the instrument to be "hooked on" the conductor without disconnecting it. Therefore, the current flowing through the conductor may be measured safely and easily, as shown in figure 1-43.

Figure 1-43 A hook-on type voltammeter

p. 75

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-66 UNCLASSIFIED The instrument is usually constructed so that voltages also may be measured. However, in order to read voltage, the meter switch must be set to VOLTS, and leads must be connected from the voltage terminals on the meter to terminals across which the voltage is to be measured.

1.3.16.2 Wattmeter Electric power is measured by means of a wattmeter. This instrument is of the electrodynamic type. It consists of a pair of fixed coils, known as current coils, and a movable coil known as the potential coil. (See fig. 1-44.)

Figure 1-44 A simplified electrodynamic wattmeter circuit

p. 76

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-67 UNCLASSIFIED The fixed coils are made up of a few turns of a comparatively large conductor. The potential coil consists of many turns of fine wire. It is mounted on a shaft, carried in jeweled bearings, so that it may turn inside the stationary coils. The movable coil carries a needle which moves over a suitably marked scale. Spiral coil springs hold the needle to a zero position.

The current coil (stationary coil) of the wattmeter is connected in series with the circuit (load), and the potential coil (movable coil) is connected across the line. When line current flows through the current coil of a wattmeter, a field is set up around the coil. The strength of this field is proportional to the line current and in phase with it. The potential coil of the wattmeter generally has a high-resistance resistor connected in series with it. This is for the purpose of making the potential-coil circuit of the meter as purely resistive as possible. As a result, current in the potential circuit is practically in phase with line voltage. Therefore, when voltage is applied to the potential circuit, current is proportional to and in phase with the line voltage.

The actuating force of a wattmeter comes from the field of its current coil and the field of its potential coil. The force acting on the movable coil at any instant (tending to turn it) is proportional to the instantaneous values of line current and voltage.

The wattmeter consists of two circuits, either of which will be damaged if too much current is passed through them. This fact is to be especially emphasized in the case of wattmeters, because the reading of the instrument does not serve to tell the user that the coils are being overheated. If an ammeter or voltmeter is overloaded, the pointer will be indicating beyond the upper limit of its scale. In the wattmeter, both the current and potential circuits may be carrying such an overload that their insulation is burning, and yet the pointer may be only part way up the scale. This is because the position of the pointer depends upon the power factor of the circuit as well as upon the voltage and current. Thus, a low power-factor circuit will give a very low reading on the wattmeter even when the current and potential circuits are loaded to the maximum safe limit. This safe rating is generally given on the face of the instrument. A wattmeter is always distinctly rated, not in watts but in volts and amperes. Figure 1-45 shows the proper way to connect a wattmeter in various circuits.

p. 77

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-68 UNCLASSIFIED

1.3.16.3 Watt-Hour Meter The watt-hour meter is an instrument for measuring energy. Since energy is the product of power and time, the watt-hour meter must take into consideration both of these factors.

In principle, the watt-hour meter is a small motor whose instantaneous speed is proportional to the POWER passing through it. The total revolutions in a given time are proportional to the total ENERGY, or watt-hours, consumed during that time.

The following directions should be followed when reading the dials of a watt-hour meter. The meter, in this case, is a four-dial type.

The pointer on the right-hand dial (fig. 1-46) registers 1 kilowatt-hour, or 1,000 watt- hours, for each division of the dial. A complete revolution of the hand on this dial will move the hand of the second dial one division and register 10 kilowatt-hours, or 10,000 watt-hours. A complete revolution of the hand of the second dial will move the third hand one division and register 100 kilowatt-hours or 100,000 watt-hours, and so on.

Figure 1-45 A wattmeter connected in various circuits. TWO-PHASE SYSTEM

p. 78

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-69 UNCLASSIFIED

Accordingly, you must read the hands from left to right, and add three zeros to the reading of the lowest dial to obtain the reading of the meter in watt-hours. The dial hands should always be read as indicating the figure which they have LAST PASSED, and not the one they are approaching.

Q60. Why would you use a hook-on voltammeter instead of a multimeter? Q61. What electrical quantity is measured by a wattmeter? Q62. What electrical quantity is measured by a watt-hour meter? Q63. What is the quantity shown on the watt-hour meter in figure 1-46? Figure 1-46 Watt-hour meter

p. 79

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-70 UNCLASSIFIED 1.3.16.4 Frequency Meters All alternating voltage sources are generated at a set frequency or range of frequencies. A frequency meter provides a means of measuring this frequency. Two common types of frequency meters are the vibrating-reed frequency meter and the moving-disk frequency meter.

1.3.16.4.1 Vibrating-Reed Frequency Meter The vibrating-reed frequency meter is one of the simplest devices for indicating the frequency of an ac source. Vibrating-reed frequency meters are usually in-circuit meters. They are used on power panels to monitor the frequency of ac. A simplified diagram of one type of vibrating-reed frequency meter is shown in figure 1-47.

Figure 1-47 Simplified disc of a vibrating-reed frequency meter. INDICATOR DIAL

p. 80

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-71 UNCLASSIFIED The current whose frequency is to be measured flows through the coil and exerts maximum attraction on the soft-iron armature TWICE during each cycle (fig. 1-47(A)). The armature is attached to the bar, which is mounted on a flexible support. Reeds having natural vibration frequencies of 110, 112, 114, and so forth, up to 130 hertz are mounted on the bar (fig. 1-47(B)). The reed having a frequency of 110 hertz is marked 55 hertz; the one having a frequency of 112 hertz is marked 56 hertz; the one having a frequency of 120 hertz is marked 60 hertz; and so forth.

When the coil is energized with a current having a frequency between 55 and 65 hertz, all the reeds are vibrated slightly; but, the reed having a natural frequency closest to that of the energizing current (whose frequency is to be measured) vibrates more.

The frequency is read from the scale value opposite the reed having the greatest vibration.

In some instruments the reeds are the same lengths, but are weighted by different amounts at the top so that they will have different natural rates of vibration.

An end view of the reeds is shown in the indicator dial of figure 1-47(C). If the current has a frequency of 60 hertz per second, the reed marked "60" hertz will vibrate the amount, as shown.

p. 81

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-72 UNCLASSIFIED 1.3.16.4.2 Moving-Disk Frequency Meter Moving-disk frequency meters are most commonly out-of-circuit meters. They can be used to spot check the frequency of power sources or equipment signals.

A moving-disk frequency meter is shown in figure 1-48. One coil tends to turn the disk clockwise, and the other, counterclockwise. Magnetizing coil A is connected in series with a large value of resistance. Coil B is connected in series with a large inductance and the two circuits are supplied in parallel by the source.

For a given voltage, the current through coil A is practically constant. However, the current through coil B varies with the frequency. At a higher frequency the inductive reactance is greater and the current through coil B is less; the reverse is true at a lower frequency. The disk turns in the direction determined by the stronger coil.

Figure 1-48 Simplified diagram of a moving-disk frequency meter

p. 82

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-73 UNCLASSIFIED A perfectly circular disk would tend to turn continuously. This is not desirable, and so the disk is constructed so that it will turn only a certain amount clockwise or counterclockwise about the center position, which is commonly marked 60 hertz on commercial equipment. To prevent the disk from turning more than the desired amount, the left half of the disk is mounted so that when motion occurs, the same amount of disk area will always be between the poles of coil A. Therefore, the force produced by coil A to rotate the disk is constant for a constant applied voltage. The right half of the disk is offset, as shown in the figure. When the disk rotates clockwise, an increasing area will come between the poles of coil B; when it rotates counterclockwise, a decreasing area will come between the poles of coil B. The greater the area between the poles, the greater will be the disk current and the force tending to turn the disk.

If the frequency applied to the frequency meter should decrease, the reactance offered by L would decrease and the field produced by coil B would increase. The field produced by coil A would remain the same. Thus, the force produced by coil B would tend to move the disk and the pointer counterclockwise until the area between the poles was reduced enough to make the two forces equal. The scale is calibrated to indicate the correct frequency.

If the frequency is constant and the voltage is changed, the currents in the two coils-and therefore the opposing forces-change by the same amount. Thus, the indication of the instrument is not affected by a change in voltage.

p. 83

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-74 UNCLASSIFIED Q64. What are two types of frequency meters? Q65. What type of meter is shown and what is the value of the quantity being measured for each meter in figure1-49?

Figure 1-49 Meter recognition

p. 84

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-75 UNCLASSIFIED Q66. What meter reading is shown on each multimeter in each part of figure 1-50? Q67. Which part of figure1-50 shows the switch positions the multimeter should be left in when the meter is secured?

Figure 1-50 Multimeter reading practice

p. 85

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-76 UNCLASSIFIED Q68. What type of meter is shown and what is the value of the quantity being measured for each meter in figure 1-51? Q69. If the insulation of a conductor was being measured in figure1-51 (A), would the reading indicate a good insulation?

Figure 1-51 Meter reading practice

p. 86

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-77 UNCLASSIFIED Q70. What type of frequency meter is shown and what is the value indicated for each meter in figure 1-52?

Figure 1-52 Frequency meter reading

p. 87

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-78 UNCLASSIFIED 1.4 SUMMARY The important points of this chapter are summarized in the following summary. You should be familiar with these points before continuing with the study of electricity.

CIRCUIT MEASUREMENT is used to monitor the operation of a piece of electrical or electronic equipment and determine the reason the equipment is not functioning properly. In-circuit meters monitor the operation of equipment and out-of-circuit meters can be used on more than one device.

A compass will react to the magnetic field around a conducting wire. As the current increases, the compass movement increases. If the current decreases, the compass movement is less. If the current direction changes, the compass movement changes direction. PERMANENT-MAGNET MOVING-COIL meter movement (d’Arsonval movement) uses the interaction of magnetic fields to produce movement.

If a compass is placed close to a conductor with ac, the compass will follow the current alternations if the ac is of low frequency. A rectifier will allow the compass to react to the average value of the ac.

DAMPING is used to smooth out the vibration and to help prevent overshooting of the meter pointer. Damping in a d’Arsonval meter movement is accomplished by the emf caused by the coil movement. A second damping system uses a vane attached to the coil in an airtight chamber. A meter movement reacts to the average value of ac, but the scale is calibrated to read the effective (rms) value.

There are meter movements that will measure either ac or dc without the use of a rectifier. They are the ELECTRODYNAMIC, MOVING-VANE, and HOT-WIRE or THERMOCOUPLE movements.

Electrodynamic meter movements are usually used in wattmeters. They operate much like a d’Arsonval meter movement, except field coils are used instead of a permanent magnet.

The moving-vane meter movement operates on the principle of magnetic repulsion of like poles. This movement will measure either current or voltage.

The hot-wire movement is only used to measure current. It is based on the expansion of a wire heated by current through the wire.

The thermocouple movement uses the current being developed in a thermocouple when the heat of a resistive wire is transferred to the thermocouple. The developed current is measured by a very sensitive dc ammeter. This movement will measure only current.

p. 88

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-79 UNCLASSIFIED An AMMETER measures current. It is always connected in series with the circuit being measured. An ammeter should have a small resistance so the effect of the ammeter on the circuit will be kept to a minimum. Ammeter sensitivity is the amount of current that causes 0 full scale deflection of the ammeter. Shunt F resistors are used to provide an ammeter’s ranges.

The following SAFETY PRECAUTIONS should be observed when using an ammeter.

• Always connect an ammeter in series. • Always start with the highest range. • Deenergize and discharge the circuit before connecting or disconnecting an ammeter. • Never use a dc ammeter to measure ac. • In dc ammeters, observe the proper polarity.

VOLTMETERS are used to measure voltage. They are always connected in parallel with the circuit being measured. A voltmeter should have a high resistance compared to the circuit being measured to minimize the loading effect . Since the resistance of a meter movement is constant, a voltmeter can be made from a current-sensitive meter movement by the use of range resistors and an appropriate scale. Voltmeter sensitivity is expressed in ohms per volt.

An electrostatic meter movement reacts to voltage rather than current and is used only for high-voltage measurements. The following SAFETY PRECAUTIONS should be observed when using a voltmeter.

• Always connect a voltmeter in parallel. • Always start with the highest range. • Deenergize and discharge the circuit before connecting or disconnecting the voltmeter. • Never use a dc voltmeter to measure an ac voltage. • On a dc voltmeter, observe the proper polarity.

OHMMETERS are used to measure resistance and to check continuity. An ohmmeter is connected in series with the resistance being measured. The ohmmeter range which allows a midscale indication should be selected. Resistors are used to allow an ohmmeter to have several ranges. In a SERIES OHMMETER the resistors are used in series with the resistance being measured. Series ohmmeters have the 0 indication on the right side of the scale.

A SHUNT OHMMETER’s internal range resistors are in parallel with the resistance being measured. A shunt ohmmeter will have the 0 indication on the left side of the scale.

p. 89

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-80 UNCLASSIFIED The following SAFETY PRECAUTIONS should be observed when using an ohmmeter.

• Deenergize and discharge the circuit before connecting an ohmmeter. • Do not apply power while measuring resistance. • Switch ohmmeters OFF, if a setting is provided, or to the highest range and remove the meter leads from the meter when finished measuring resistance. • Adjust the ohmmeter after changing ranges and before measuring resistance.

A MEGOHMMETER (MEGGER) is used to measure very large resistances, such as the insulation of wiring. To use a megger, isolate the resistance being measured from other circuits, connect the meter leads, turn the hand crank, and note the meter indication. Normal insulation will indicate infinity.

The following SAFETY PRECAUTIONS should be observed when using a megger. Use meggers for high-resistance measurements only.

• Never touch the test leads while the handle is being cranked. • Deenergize and discharge the circuit completely before connecting a megger. • Disconnect the item being checked from other circuitry, if possible, before using megger.

A MULTIMETER is a single meter that combines the functions of a dc ammeter, a dc voltmeter, an ac ammeter, an ac voltmeter, and an ohmmeter. It is more convenient to have one meter with several functions than several meters each with a single function. The various functions of a multimeter are selected by use of the appropriate function switch positions, jacks, and meter scales. A mirror may be used on the scale of a multimeter to eliminate parallax error.

The following SAFETY PRECAUTIONS should be observed when using a multimeter.

• Deenergize and discharge the circuit completely before connecting a multimeter. • Never apply power to the circuit while measuring resistance with a multimeter. • Connect the multimeter in series with the circuit for current measurements and in parallel for voltage measurements. • Be certain the multimeter is switched to ac before attempting to measure ac circuits. • Observe proper dc polarity when measuring dc circuits. • When you are finished with a multimeter, switch it to the OFF position, if available. If there is no OFF position, switch the multimeter to the highest ac voltage position. • Always start with the highest voltage or current range. • Select a final range that allows a reading near the middle of the scale.

p. 90

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-81 UNCLASSIFIED • Adjust the "0 ohms" reading after changing resistance ranges and before making a resistance measurement. • Be certain to read ac measurements on the ac scale of a multimeter.

A HOOK-ON TYPE VOLTAMMETER allows you to measure current safely and easily (with no need to disconnect the wiring of the circuit). A hook-on type voltammeter uses a split-core transformer to measure current.

A WATTMETER is usually an electrodynamic meter and is used to measure power.

A WATT-HOUR METER is basically a small motor whose instantaneous speed is proportional to the power through the motor. The total revolutions in a given time are proportional to the total energy, or watt-hours, used during that time. Watt-hour meters measure energy.

FREQUENCY METERS are used to measure the frequency of an ac signal. The two basic types are the vibrating-reed frequency meter which is usually used as an in-circuit meter, and the moving-disk frequency meter which is usually used as an out-of-circuit meter.

p. 91

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-82 UNCLASSIFIED ANSWERS TO QUESTIONS Q1. THROUGH Q70.

A1. Circuit measurement is used to (1) monitor the operation of a piece of electrical or electronic equipment and (2) determine the reason a piece of electrical or electronic equipment is not functioning properly.

A2. In-circuit meters are used to monitor the operation of electrical or electronic devices.

A3. Out-of-circuit meters can be used on more than one electrical or electronic device.

A4. The compass needle swings away from magnetic north and aligns itself with the magnetic field around the conductor.

A5. If the current increases the magnetic field increases; if the current decreases the magnetic field decreases.

A6. The compass needle will not be deflected as far from magnetic north.

A7. A permanent-magnet moving-coil meter movement used in most electrical and electronic meters.

A8. A magnetic field is generated around the coil and the attraction of this field with the permanent magnet causes the coil to move.

A9. To return the pointer to its rest position when there is no current flow; to oppose the coil movement when there is current flow; to provide electrical connections for the coil.

A10. The compass needle would swing back and forth as the current changed from positive to negative.

A11. The compass needle would vibrate rapidly around the zero-current point ac meter (magnetic north).

A12. A rectifier changes alternating current to pulsating direct current and allows a dc meter to measure ac.

A13. By the use of a rectifier

A14. The process of "smoothing out" the oscillation in a meter movement.

A15. As the coil moves through the field of the permanent magnet, a current is induced in the coil opposing the movement of the coil; and a vane can be attached to the coil and placed in the airtight chamber so that the movement of the vane opposes the movement of the coil.

p. 92

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-83 UNCLASSIFIED A16. Average value.

A17. Effective value (rms).

A18. Electrodynamic, moving vane, and hot-wire or thermocouple.

A19. Current.

A20. Current.

A21. In series.

A22. Since the ammeter is a resistor in series with the load, it increases the resistance of the circuit and lowers circuit current.

A23. The resistance of the ammeter must be much smaller than the circuit load.

A24. The amount of current that will cause full-scale deflection.

A25. Shunt resistors (internal or external).

A26. To prevent damage to the meter movement from excessive current.

A27. A range that allows a meter reading near the center of the scale.

A28.

a. Always connect an ammeter in series. b. Always start with the highest range. c. In dc ammeters, observe the proper polarity. d. Deenergize and discharge the circuit before connecting or disconnecting the ammeter. e. Never use a dc ammeter to measure ac current. f. Observe the general safety precautions of electric and electronic devices.

A29. Since the ammeter has a small resistance compared to the load, it will have very high current if it is connected in parallel. This high current will damage the meter.

A30. Voltage.

A31. In parallel.

A32. The connection of a voltmeter adds a resistance in parallel with the circuit changing the total circuit resistance, and loads the circuit.

p. 93

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-84 UNCLASSIFIED A33. A voltmeter must have a high resistance compared to the circuit being measured.

A34. Since the resistance of a meter movement remains the same as the pointer is deflected, the amount of current through the movement is proportional to the voltage applied. Therefore, only the scale of the movement must be changed.

A35. It is an indication of the resistance of the meter expressed in ohms per volt. The total resistance of the meter is the sensitivity multiplied by the full-scale voltage.

A36. The use of resistors in series with the meter movement.

A37. To prevent excess current through the meter movement.

A38. Electrostatic.

A39. High-voltage measurement.

A40.

a. Always connect a voltmeter in parallel. b. Always start with the highest range. c. Deenergize and discharge the circuit before connecting or disconnecting the voltmeter. d. In a dc voltmeter, observe the proper polarity. e. Never use a dc voltmeter to measure ac voltage. f. Observe the general safety precautions of electric and electronic devices.

A41. Resistance.

A42. Circuit continuity.

A43. The ohmmeter is connected in series with the resistance to be measured.

A44. An ohmmeter has several internal range resistors and a switch or a series of jacks to select the proper range.

A45. The middle of the scale.

A46. Series and shunt.

A47. Series ohmmeters have 0 on the right end of the scale and ∞ on the left end of the scale. Shunt ohmmeters are the opposite.

p. 94

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-85 UNCLASSIFIED A48.

a. Deenergize and discharge the circuit before connecting an ohmmeter. b. Do not apply power to a circuit while measuring resistance. c. Switch ohmmeters to the OFF position, if provided, or to highest range and remove meter leads from the meter when finished measuring resistance. d. Adjust the ohmmeter after changing resistance range and before measuring reading indicates the resistance.

A49. To measure high resistance.

A50. Connect one lead to the insulation and one lead to the conductor. Turn the hand- crank until it starts to slip. Note the reading.

A51. Infinity.

A52.

a. Use meggers for high-resistance measurement only. b. Never touch the test leads when the handle is being cranked. c. Deenergize and discharge the circuit completely before connecting a megger. d. Disconnect the item being checked from other circuitry, if possible, before using a megger.

A53. A single measuring device capable of performing the functions of a dc voltmeter and ammeter, an ac voltmeter and ammeter, and an ohmmeter.

A54. It is much more convenient to have one meter with several functions than several meters each with a single function.

A55. By changing the position of the function switch.

A56. The meter movement reacts to average ac voltage and current and the effective value is desired.

A57. To stop parallax error

A58. Make sure no image of the pointer is visible in the mirror when reading the meter.

p. 95

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-86 UNCLASSIFIED A59.

a. Deenergize and discharge the circuit completely before connecting or disconnecting a multimeter. b. Never apply power to the circuit while measuring resistance with a multimeter. c. Connect the multimeter in series with the circuit for current measurements, and in parallel for voltage measurements. d. Be certain the multimeter is switched to ac before attempting to measure ac circuits. e. Observe proper dc polarity when measuring dc. f. When you are finished with a multimeter, switch it to the OFF position, if available. If there is no OFF position, switch the multimeter to the highest ac voltage position. g. Always start with the highest voltage or current range. h. Select a final range that allows a reading near the middle of the scale. i. Adjust the "0 ohms" reading after changing resistance ranges and before making a resistance measurement. j. Be certain to read ac measurements on the ac scale of a multimeter. k. Observe the general safety precautions for electrical and electronic devices.

A60. To measure current safely and easily (with no need to disconnect the wiring of the circuit).

A61. Power.

A62. Energy.

A63. 5.945 megawatt-hours, or 5,945 kilowatt-hours, or 5,945, 000 watt-hours.

A64. Vibrating reed and moving disk.

A65.

a. A dc ammeter, 90 mA dc b. A dc voltmeter, 200 V dc c. An ac voltmeter, 4.6 V ac d. An ohmmeter, 400 ohms

A66. (A) 410 mA dc; (B) 3.9 mA ac; (C) -22 V dc; (D) 600 V ac; (E) 1.4 V ac; (F) 1.9 kohms (1900Ω)

A67. Figure1-50(D).

p. 96

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

1-87 UNCLASSIFIED A68. (A) Megger (megohmmeter), infinity; (B) Wattmeter, 9.5 kilowatts (9,500 watts). (C) Watt-hour meter, 2.693 megawatt-hours 2,693 kilowatt-hours) (2,693,000 watt- hours).

A69. Yes.

A70. (A) Vibrating-reed, 60Hz. (B) Moving-disk, 58 Hz.

Chapter 2 Circuit Protection Devices

p. 97

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-1 UNCLASSIFIED 2 CIRCUIT PROTECTION DEVICES LEARNING OBJECTIVES

Upon completion of this chapter you will be able to:

1. State the reasons circuit protection is needed and three conditions requiring circuit protection. 2. Define a direct short, an excessive current condition, and an excessive heat condition. 3. State the way in which circuit protection devices are connected in a circuit. 4. Identify two types of circuit protection devices and label the schematic symbols for each type. 5. Identify a plug-type and a cartridge-type fuse (open and not open) from illustrations. 6. List the three characteristics by which fuses are rated and state the meaning of each rating. Identify a plug-type and a cartridge-type fuse (open and not open) from illustrations. 7. List the three categories of time delay rating for fuses and state a use for each type of time-delay rated fuse. 8. List the three categories of time delay rating for fuses and state a use for each type of time-delay rated fuse. Identify fuses as to voltage, current, and time delay ratings using fuses marked with the old military, new military, old commercial, and new commercial systems. List the three categories of time delay rating for fuses and state a use for each type of time-delay rated fuse. 9. Identify a clip-type and a post-type fuse holder from illustrations and identify the connections used on a post-type fuse holder for power source and load connections. 10. List the methods of checking for an open fuse, the items to check when replacing a fuse, the safety precautions to be observed when checking and replacing fuses, and the conditions to be checked for when conducting preventive maintenance on fuses. 11. Select a proper replacement and substitute fuse from a listing of fuses. 12. List the five main components of a circuit breaker and the three types of circuit breaker trip elements. 13. Describe the way in which each type of trip element reacts to excessive current. 14. Define the circuit breaker terms trip-free and nontrip-free and state one example for the use of each of these types of circuit breakers. 15. List the three time delay ratings of circuit breakers. 16. Define selective tripping, state why it is used, and state the way in which the time delay ratings of circuit breakers are used to design a selective tripping system. 17. Identify the factors used in selecting circuit breakers. 18. List the steps to follow before starting work on a circuit breaker and the items to be checked when maintaining circuit breakers.

p. 98

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-2 UNCLASSIFIED 2.1 INTRODUCTION Electricity, like fire, can be either helpful or harmful to those who use it. A fire can keep people warm and comfortable when it is confined in a campfire or a furnace. It can be dangerous and destructive if it is on the loose and uncontrolled in the woods or in a building. Electricity can provide people with the light to read by or, in a blinding flash, destroy their eyesight. It can help save people’s lives, or it can kill them. While we take advantage of the tremendous benefits electricity can provide, we must be careful to protect the people and systems that use it.

It is necessary then, that the mighty force of electricity be kept under control at all times. If for some reason it should get out of control, there must be a method of protecting people and equipment. Devices have been developed to protect people and electrical circuits from currents and voltages outside their normal operating ranges. Some examples of these devices are discussed in this chapter.

An electrical unit is built with great care to ensure that each separate electrical circuit is fully insulated from all the others. This is done so that the current in a circuit will follow its intended path. Once the unit is placed into service, however, many things can happen to alter the original circuitry. Some of the changes can cause serious problems if they are not detected and corrected. While circuit protection devices cannot correct an abnormal current condition, they can indicate that an abnormal condition exists and protect personnel and circuits from that condition. In this chapter, you will learn what circuit conditions require protection devices and the types of protection devices used.

While you study this chapter, it should be kept in mind that a circuit protection device is used to keep an undesirably large current, voltage, or power surge out of a given part of an electrical circuit.

2.2 CIRCUIT CONDITIONS REQUIRING PROTECTION DEVICES As has been mentioned, many things can happen to electrical and electronic circuits after they are in use. Chapter 1 of this module contains information showing you how to measure circuit characteristics to help determine the changes that can occur in them. Some of the changes in circuits can cause conditions that are dangerous to the circuit itself or to people living or working near the circuits. These potentially dangerous conditions require circuit protection. The conditions that require circuit protection are direct shorts, excessive current, and excessive heat.

p. 99

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-3 UNCLASSIFIED 2.2.1 Direct Short One of the most serious troubles that can occur in a circuit is a DIRECT SHORT. Another term used to describe this condition is a SHORT CIRCUIT. The two terms mean the same thing and, in this chapter, the term direct short will be used. This term is used to describe a situation in which some point in the circuit, where full system voltage is present, comes in direct contact with the ground or return side of the circuit. This establishes a path for current flow that contains only the very small resistance present in the wires carrying the current.

According to Ohm’s law, if the resistance in a circuit is extremely small, the current will be extremely large. Therefore, when a direct short occurs, there will be a very large current through the wires. Suppose, for instance, that the two leads from a battery to a motor came in contact with each other. If the leads were bare at the point of contact, there would be a direct short. The motor would stop running because all the current would be flowing through the short and none through the motor. The battery would become discharged quickly (perhaps ruined) and there could be the danger of fire or explosion.

The battery cables in our example would be large wires capable of carrying heavy currents. Most wires used in electrical circuits are smaller and their current carrying capacity is limited. The size of wire used in any given circuit is determined by space considerations, cost factors, and the amount of current the wire is expected to carry under normal operating conditions. Any current flow greatly in excess of normal, such as there would be in the case of a direct short, would cause a rapid generation of heat in the wire.

If the excessive current flow caused by the direct short is left unchecked, the heat in the wire will continue to increase until some portion of the circuit burns. Perhaps a portion of the wire will melt and open the circuit so that nothing is damaged other than the wire involved. The probability exists, however, that much greater damage will result. The heat in the wire can char and burn the insulation of the wire and that of other wires bundled with it, which can cause more shorts. If a fuel or oil leak is near any of the hot wires, a disastrous fire might be started.

p. 100

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-4 UNCLASSIFIED 2.2.2 Excessive Current It is possible for the circuit current to increase without a direct short. If a resistor, capacitor, or inductor changes value, the total circuit impedance will also change in value. If a resistor decreases in ohmic value, the total circuit resistance decreases. If a capacitor has a dielectric leakage, the capacitive reactance decreases. If an inductor has a partial short of its winding, inductive reactance decreases. Any of these conditions will cause an increase in circuit current. Since the circuit wiring and components are designed to withstand normal circuit current, an increase in current would cause overheating (just as in the case of a direct short). Therefore, excessive current without a direct short will cause the same problems as a direct short.

2.2.3 Excessive Heat As you have read, most of the problems associated with a direct short or excessive current concern the heat generated by the higher current. The damage to circuit components, the possibility of fire, and the possibility of hazardous fumes being given off from electrical components are consequences of excessive heat. It is possible for excessive heat to occur without a direct short or excessive current. If the bearings on a motor or generator were to fail, the motor or generator would overheat. If the temperature around an electrical or electronic circuit were to rise (through failure of a cooling system for example), excessive heat would be a problem. No matter what the cause, if excessive heat is present in a circuit, the possibility of damage, fire, and hazardous fumes exists.

Q1. Why are circuit protection devices necessary? Q2. What are the three conditions that require circuit protection? Q3. What is a direct short? Q4. What is an excessive current condition? Q5. What is an excessive heat condition?

p. 101

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-5 UNCLASSIFIED 2.3 CIRCUIT PROTECTION DEVICES All of the conditions mentioned are potentially dangerous and require the use of circuit protection devices. Circuit protection devices are used to stop current flow or open the circuit. To do this, a circuit protection device must ALWAYS be connected in series with the circuit it is protecting. If the protection device is connected in parallel, current will simply flow around the protection device and continue in the circuit.

A circuit protection device operates by opening and interrupting current to the circuit. The opening of a protection device shows that something is wrong in the circuit and should be corrected before the current is restored. When a problem exists and the protection device opens, the device should isolate the faulty circuit from the other unaffected circuits, and should respond in time to protect unaffected components in the faulty circuit. The protection device should NOT open during normal circuit operation.

The two types of circuit protection devices discussed in this chapter are fuses and circuit breakers.

Fuses - A fuse is the simplest circuit protection device. It derives its name from the Latin word "fusus," meaning "to melt." Fuses have been used almost from the beginning of the use of electricity. The earliest type of fuse was simply a bare wire between two connections. The wire was smaller than the conductor it was protecting and, therefore, would melt before the conductor it was protecting was harmed. Some "copper fuse link" types are still in use, but most fuses no longer use copper as the fuse element (the part of the fuse that melts). After changing from copper to other metals, tubes or enclosures were developed to hold the melting metal. The enclosed fuse made possible the addition of filler material, which helps to contain the arc that occurs when the element melts.

For many low power uses, the finer material is not required. A simple glass tube is used. The use of a glass tube gives the added advantage of being able to see when a fuse is open. Fuses of this type are commonly found in automobile lighting circuits.

Figure 2-1 shows several fuses and the symbols used on schematics.

p. 102

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-6 UNCLASSIFIED

Circuit Breakers - While a fuse protects a circuit, it is destroyed in the process of opening the circuit. Once the problem that caused the increased current or heat is corrected, a new fuse must be placed in the circuit. A circuit protection device that can be used more than once solves the problems of replacement fuses. Such a device is safe, reliable, and tamper proof. It is also resettable, so it can be reused without replacing any parts. This device is called a CIRCUIT BREAKER because it breaks (opens) the circuit.

The first compact, workable circuit breaker was developed in 1923. It took 4 years to design a device that would interrupt circuits of 5000 amperes at 120 volts ac or dc. In 1928 the first circuit breaker was placed on the market.

Figure 2-1 Typical fuses and schematic symbols

p. 103

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-7 UNCLASSIFIED A typical circuit breaker and the appropriate schematic symbols are shown in figure 2-2.

Q6. How are circuit protection devices connected to the circuit they are intended to protect and why are they connected in this way? Q7. What are the two types of circuit protection devices?

Figure 2-2 Typical circuit breaker and schematic symbols

p. 104

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-8 UNCLASSIFIED Q8. Label the schematic symbols shown in figure 2-3 below.

2.3.1 Fuses

2.3.1.1 Fuses Types Fuses are manufactured in many shapes and sizes. In addition to the copper fuse link already described, figure 2-1 shows other fuse types. While the variety of fuses may seem confusing, there are basically only two types of fuses: plug-type fuses and cartridge fuses. Both types of fuses use either a single wire or a ribbon as the fuse element (the part of the fuse that melts). The condition (good or bad) of some fuses can be determined by visual inspection. The condition of other fuses can only be determined with a meter. In the following discussion, visual inspection will be described. The use of meters to check fuses will be discussed later in this chapter.

Figure 2-3 Schematic symbols

p. 105

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-9 UNCLASSIFIED 2.3.1.1.1 Plug-Type Fuse The plug-type fuse is constructed so that it can be screwed into a socket mounted on a control panel or electrical distribution center. The fuse link is enclosed in an insulated housing of porcelain or glass. The construction is arranged so the fuse link is visible through a window of mica or glass. Figure 2-4 shows a typical plug-type fuse.

Figure 2-4, view A, shows a good plug-type fuse. Notice the construction and the fuse link. In figure 2-4, view B, the same type of fuse is shown after the fuse link has melted. Notice the window showing the indication of this open fuse. The indication could be either of the ones shown in figure 2-4, view B.

The plug-type fuse is used primarily in low-voltage, low-current circuits. The operating range is usually up to 150 volts and from 0.5 ampere to 30 amperes. This type of fuse is found in older circuit protection devices and is rapidly being replaced by the circuit breaker.

Figure 2-4 Plug-type fuses

p. 106

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-10 UNCLASSIFIED 2.3.1.1.2 Cartridge Fuse The cartridge fuse operates exactly like the plug-type fuse. In the cartridge fuse, the fuse link is enclosed in a tube of insulating material with metal ferrules at each end (for contact with the fuse holder). Some common insulating materials are glass, bakelite, or a fiber tube filled with insulating powder.

Figure 2-5 shows a glass-tube fuse. In figure 2-5, view A, notice the fuse link and the metal ferrules. Figure 2-5, view B, shows a glass-tube fuse that is open. The open fuse link could appear either of the ways shown in figure 2-5, view B.

Cartridge fuses are available in a variety of physical sizes and are used in many different circuit applications. They can be rated at voltages up to 10,000 volts and have current ratings of from 1/500 (.002) ampere to 800 amperes. Cartridge fuses may also be used to protect against excessive heat and open at temperatures of from 165° F to 410°F (74°C to 210°C).

Figure 2-5 Cartridge-tube fuse

p. 107

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-11 UNCLASSIFIED Q9. Label the fuses shown in figure 2-6 according to type. Q10. Identify the open fuses shown in figure 2-6.

2.3.1.2 Fuse Ratings You can determine the physical size and type of a fuse by looking at it, but you must know other things about a fuse to use it properly. Fuses are rated by current, voltage, and time-delay characteristics to aid in the proper use of the fuse. To select the proper fuse, you must understand the meaning of each of the fuse ratings.

2.3.1.2.1 Current Rating The current rating of a fuse is a value expressed in amperes that represents the current the fuse will allow without opening. The current rating of a fuse is always indicated on the fuse.

Figure 2-6 Fuse recognition

p. 108

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-12 UNCLASSIFIED To select the proper fuse, you must know the normal operating current of the circuit. If you wish to protect the circuit from overloads (excessive current), select a fuse rated at 125 percent of the normal circuit current. In other words, if a circuit has a normal current of 10 amperes, a 12.5-ampere fuse will provide overload protection. If you wish to protect against direct shorts only, select a fuse rated at 150 percent of the normal circuit current. In the case of a circuit with 10 amperes of current, a 15 ampere fuse will protect against direct shorts, but will not be adequate protection against excessive current.

2.3.1.2.2 Voltage Rating The voltage rating of a fuse is NOT an indication of the voltage the fuse is designed to withstand while carrying current. The voltage rating indicates the ability of the fuse to quickly extinguish the arc after the fuse element melts and the maximum voltage the open fuse will block. In other words, once the fuse has opened, any voltage less than the voltage rating of the fuse will not be able to "jump" the gap of the fuse. Because of the way the voltage rating is used, it is a maximum rms voltage value. You must always select a fuse with a voltage rating equal to or higher than the voltage in the circuit you wish to protect.

2.3.1.2.3 Time Delay Rating There are many kinds of electrical and electronic circuits that require protection. In some of these circuits, it is important to protect against temporary or transient current increases. Sometimes the device being protected is very sensitive to current and cannot withstand an increase in current. In these cases, a fuse must open very quickly if the current increases.

Some other circuits and devices have a large current for short periods and a normal (smaller) current most of the time. An electric motor, for instance, will draw a large current when the motor starts, but normal operating current for the motor will be much smaller. A fuse used to protect a motor would have to allow for this large temporary current, but would open if the large current were to continue.

Fuses are time delay rated to indicate the relationship between the current through the fuse and the time it takes for the fuse to open. The three time delay ratings are delay, standard, and fast.

p. 109

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-13 UNCLASSIFIED 2.3.1.2.3.1 Delay A delay, or slow-blowing, fuse has a built-in delay that is activated when the current through the fuse is greater than the current rating of the fuse. This fuse will allow temporary increases in current (surge) without opening. Some delay fuses have two elements; this allows a very long time delay. If the overcurrent condition continues, a delay fuse will open, but it will take longer to open than a standard or a fast fuse.

Delay fuses are used for circuits with high surge or starting currents, such as motors, solenoids, and transformers.

2.3.1.2.3.2 Standard Standard fuses have no built-in time delay. Also, they are not designed to be very fast acting. Standard fuses are sometimes used to protect against direct shorts only. They may be wired in series with a delay fuse to provide faster direct short protection. For example, in a circuit with a 1-ampere delay fuse, a 5-ampere standard fuse may be used in addition to the delay fuse to provide faster protection against a direct short.

A standard fuse can be used in any circuit where surge currents are not expected and a very fast opening of the fuse is not needed. A standard fuse opens faster than a delay fuse, but slower than a fast rated fuse.

Standard fuses can be used for automobiles, lighting circuits, or electrical power circuits.

2.3.1.2.3.3 Fast Fast fuses are designed to open very quickly when the current through the fuse exceeds the current rating of the fuse. Fast fuses are used to protect devices that are very sensitive to increased current. A fast fuse will open faster than a delay or standard fuse.

Fast fuses can be used to protect delicate instruments or semiconductor devices.

p. 110

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-14 UNCLASSIFIED Figure 2-7 will help you understand the differences between delay, standard, and fast fuses. Figure 2-7 shows that, if a 1-ampere rated fuse had 2 amperes of current through it, (200% of the rated value), a fast fuse would open in about .7 second, a standard rated fuse would open in about 1.5 seconds, and a delay rated fuse would open in about 10 seconds. Notice that in each of the fuses, the time required to open the fuse decreases as the rated current increases.

Q11. In what three ways are fuses rated? Q12. What does the current rating of a fuse indicate? Q13. What does the voltage rating of a fuse indicate? Q14. What are the three time delay ratings of fuses? Q15. Give an example of a device you could protect with each type of time delay fuse.

Figure 2-7 Time required for fuse to open.

p. 111

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-15 UNCLASSIFIED 2.3.1.3 Identification of Fuses Fuses have identifications printed on them. The printing on the fuse will identify the physical size, the type of fuse, and the fuse ratings. There are four different systems used to identify fuses. The systems are the old military designation, the new military designation, the old commercial designation, and the new commercial designation. All four systems are presented here, so you will be able to identify a fuse no matter which designation is printed on the fuse.

You may have to replace an open fuse that is identified by one system with a good fuse that is identified by another system. The designation systems are fairly simple to understand and cross-reference once you are familiar with them.

2.3.1.3.1 Old Military Designation Figure 2-8 shows a fuse with the old military designation. The tables in the lower part of the figure show the voltage and current codes used in this system. The upper portion of the figure is the explanation of the old military designation. The numbers and letters in parentheses are the coding for the fuse shown in figure 2-8.

The old military designation always starts with "F," which stands for fuse. Next, the set of numbers (02) indicates the style. Style means the construction and dimensions (size) of the fuse. Following the style is a letter that represents the voltage rating of the fuse (G). The voltage code table in figure 2-8 shows each voltage rating letter and its meaning in volts. In the example shown, the voltage rating is G, which means the fuse should be used in a circuit where the voltage is 250 volts or less. After this is a set of three numbers and the letter "R," which represent the current rating of the fuse. The "R" indicates the decimal point. In the example shown, the current rating is 1R00 or 1.00 ampere. Some other examples of the current rating are shown in the current code table of figure 2-8. The final letter in the old military designation (A) indicates the time delay rating of the fuse.

While the old military designation is still found on some fuses, the voltage and current ratings must be "translated," since they use letters to represent numerical values. The military developed the new military designations to make fuse identification easier.

p. 112

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-16 UNCLASSIFIED

Figure 2-8 Old type military fuse designation

p. 113

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-17 UNCLASSIFIED 2.3.1.3.2 New Military Designation Figure 2-9 is an example of a fuse coded in the new military designation. The fuse identified in the example in figure 2-9 is the same type as the fuse used as an example in figure 2-8.

The new military designation always start with the letter "F," which stands for fuse. The set of numbers (02) next to this indicates the style. The style numbers are identical to the ones used in the old military designation and indicate the construction and dimensions of the fuse. Following the style designation is a single letter (A) that indicates the time delay rating of the fuse. This is the same time delay rating code as indicated in the old military designation, but the position of this letter in the coding is changed to avoid confusing the "A" for standard time delay with the "A" for ampere. Following the time delay rating is the voltage rating of the fuse (250) V. In the old military designation, a letter was used to indicate the voltage rating. In the new military designation, the voltage is indicated by numbers followed by a "V," which stands for volts or less. After the voltage rating, the current rating is given by numbers followed by the letter "A." The current rating may be a whole number (1A), a fraction (1/500 A), a whole number and a fraction (1 1/2A), a decimal (0.250A), or a whole number and a decimal (1.50A).

Figure 2-9 New type military fuse designation

p. 114

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-18 UNCLASSIFIED If the ferrules of the fuse are silver-plated, the current rating will be followed by the letter "S." If any other plating is used, the current rating will be the last part of the fuse identification.

As you can see, the new military designation is much easier to understand than the old military designation.

You may find a fuse coded in one of the commercial designations. The commercial designations are fairly easy to understand and figure 2-10 shows the old and new commercial designations for the same type of fuse that was used in figures 2-8 and 2-9.

Figure 2-10 Commercial designations for fuses

p. 115

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-19 UNCLASSIFIED 2.3.1.3.3 Old Commercial Designation Figure 2-10, view A, shows the old commercial designation for a fuse. The first part of the designation is a combination of letters and numbers (three in all) that indicates the style and time delay characteristics. This part of the designation (3AG) is the information contained in the style and time delay rating portions of military designations.

In the example shown, the code 3AG represents the same information as the underlined portions of F02 G 1R00 A from figure 2-8 (Old Military Designation) and F02A 250VIAS from figure 2-9 (New Military Designation). The only way to know the time delay rating of this fuse is to look it up in the manufacturer’s catalog or in a cross- reference listing to find the military designation. The catalog will tell you the physical size, the material from which the fuse is constructed, and the time delay rating of the fuse. A 3AG fuse is a glass-bodied fuse, 1/4 inch × 1 1/4 inches (6.35 millimeters × 31.8 millimeters) and has a standard time delay rating.

Following the style designation is a number that is the current rating of the fuse (1). This could be a whole number, a fraction, a whole number and a fraction, a decimal, or a whole number and a decimal. Following the current rating is the voltage rating; which, in turn, is followed by the letter "V," which stands for volts or less (250V).

2.3.1.3.4 New Commercial Designation Figure 2-10, view B, shows the new commercial designation for fuses. It is the same as the old commercial designation except for the style portion of the coding. In the old commercial system, the style was a combination of letters and numbers. In the new commercial system, only letters are used. In the example shown, 3AG in the old system becomes AGC in the new system. Since "C" is the third letter of the alphabet, it is used instead of the "3" used in the old system. Once again, the only way to find out the time delay rating is to look up this coding in the manufacturer’s catalog or to use a cross- reference listing. The remainder of the new commercial designation is exactly the same as the old commercial designation.

p. 116

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-20 UNCLASSIFIED Q16. What are the voltage, current, and time delay ratings for a fuse with the designation (a) F02DIR50B (b) 𝐹02𝐴250𝑉 1 8 𝐴 Q17. What are the voltage and current ratings for a fuse designated? (a) 3𝐴𝐺 1 16 125𝑉 (b) FNA 15 100 250𝑉 Q18. What is the new military designation for a fuse with the old military designation F05A20ROB?

p. 117

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-21 UNCLASSIFIED 2.3.1.4 Fuseholders For a fuse to be useful, it must be connected to the circuit it will protect. Some fuses are "wired in" or soldered to the wiring of circuits, but most circuits make use of FUSEHOLDERS. A fuseholder is a device that is wired into the circuit and allows easy replacement of the fuse.

Fuseholders are made in many shapes and sizes, but most fuseholders are basically either clip-type or post-type. Figure 2-11 shows a typical clip-type and post-type fuseholder.

2.3.1.4.1 Clip-Type Fuseholder The clip-type fuseholder is used for cartridge fuses. The ferrules or knife blade of the fuse are held by the spring tension of the clips. These clips provide the electrical connection between the fuse and the circuit. If a glass-bodied fuse is used, the fuse can be inspected visually for an open without removing the fuse from the fuse holder. Clip-type fuseholders are made in several sizes to hold the many styles of fuses. The clips maybe made for ferrules or knife blade cartridge fuses. While the base of a clip-type fuseholder is made from insulating material, the clips themselves are conductors. The current through the fuse goes through the clips and care must be taken to not touch the clips when there is power applied. If the clips are touched, with power applied, a severe shock or a short circuit will occur.

Figure 2-11 Typical fuseholders

p. 118

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-22 UNCLASSIFIED 2.3.1.4.2 Post-Type Fuseholders Post-type fuseholders are made for cartridge fuses. The post-type fuseholder is much safer because the fuse and fuse connections are covered with insulating material. The disadvantage of the post-type fuseholder is that the fuse must be removed to visually check for an open. The post-type fuseholder has a cap that screws onto the body of the fuseholder. The fuse is held in this cap by a spring-type connector and, as the cap is screwed on, the fuse makes contact with the body of the fuseholder. When the cap and fuse are removed from the body of the fuseholder, the fuse is removed from the circuit and there is no danger of shock or short circuit from touching the fuse.

Post-type fuseholders are usually mounted on the chassis of the equipment in which they are used. After wires are connected to the fuseholder, insulating sleeves are placed over the connections to reduce the possibility of a short circuit. Notice the two connections on the post-type fuseholder of figure 2-11. The connection on the right is called the center connector. The other connector is the outside connector. The outside connector will be closer to the equipment chassis. (The threads and nut shown are used to fasten the fuseholder to the chassis.) The possibility of the outside connector coming in contact with the chassis (causing a short circuit) is much higher than the possibility of the center conductor contacting the chassis. The power source should always be connected to the center connector so the fuse will open if the outside connector contacts the chassis. If the power source was connected to the outside connector, and the outside connector contacted the chassis, there would be a direct short, but the fuse would not open.

Q19. Label the fuseholders in figure 2-12.

Figure 2-12 Fuseholder identification

p. 119

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-23 UNCLASSIFIED Q20. Which connector should you use to connect the (a) power source and (b) load to the fuseholder shown in figure 2-12(A)? 2.3.1.5 Checking and Replacement of Fuses A fuse, if properly used, should not open unless something is wrong in the circuit the fuse is protecting. When a fuse is found to be open, you must determine the reason the fuse is open. Replacing the fuse is not enough.

Before you look for the cause of an open fuse, you must be able to determine if the fuse is open.

2.3.1.5.1 Checking for an Open Fuse There are several ways of checking for an open fuse. Some fuses and fuseholders have indicators built in to help you find an open fuse; also, a multimeter can be used to check fuses. The simplest way to check glass-bodied fuses, and the method you should use first, is visual inspection.

2.3.1.5.1.1 Visual Inspection An open glass-bodied fuse can usually be found by visual inspection. Earlier in this chapter, figures 2-4 and 2-5 showed you how an open plug-type and an open glass-bodied cartridge-type fuse would look. If the fuse element is not complete, or if the element has been melted onto the glass tube, the fuse is open.

It is not always possible to tell if a fuse is open by visual inspection. Fuses with low current ratings have elements that are so small, it is sometimes not possible to know if the fuse link is complete simply by looking at it. If the fuse is not glass-bodied, it will not be possible to check the fuse visually. Also, sometimes a fuse will look good, but will, in fact, be open. Therefore, while it is sometimes possible to know if a fuse is open by visual inspection, it is not possible to be sure a fuse is good just by looking at it.

p. 120

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-24 UNCLASSIFIED 2.3.1.5.1.2 Fuse Indicators Some fuses and fuseholders have built-in indicators to show when a fuse is open. Examples of these open-fuse indicators are shown in figure 2-13. Figure 2-13, view A, shows a cartridge-type fuse with an open-fuse indicator. The indicator is spring loaded and held by the fuse link. If the fuse link opens, the spring forces the indicator out. Some manufacturers color the indicator so it is easier to see in the open-fuse position.

Figure 2-13, view B, shows a plug-type fuseholder with an indicating lamp in the fuse cap. If the fuse opens, the lamp in the fuse cap will light. Figure 2-13, view C, shows a clip-type fuseholder with an indicating lamp.

Just as in visual checking, the indicator can show an open fuse. Since the indicator may not always work, you cannot be sure a fuse is good just because there is no open-fuse indication.

Figure 2-13 Open fuse indicators: Clip-type fuseholder with an indicating lamp

p. 121

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-25 UNCLASSIFIED 2.3.1.5.1.3 Checking Fuses with a Meter The only sure method of determining if a fuse is open is to use a meter. An ohmmeter can be used to check for an open fuse by removing the fuse from the circuit and checking for continuity through the fuse (0 ohms). If the fuse is not removed from the circuit, and the fuse is open, the ohmmeter may measure the circuit resistance. This resistance reading might lead you to think the fuse is good. You must be careful when you use an ohmmeter to check fuses with small current ratings (such as 1/32 ampere or less), because the current from the ohmmeter may be larger than the current rating of the fuse. For most practical uses, a small current capacity fuse can be checked out of the circuit through the use of a resistor. The ohmic value of the resistor is first measured and then placed in series with the fuse. The continuity reading on the ohmmeter should be of the same value, or close to it, as the original value of the resistor. This method provides protection for the fuse by dropping the voltage across the resistor. This in turn decreases the power in the form of heat at the fuse. Remember, it is heat which melts the fuse element.

A voltmeter can also be used to check for an open fuse. The measurement is taken between each end of the fuse and the common or ground side of the line. If voltage is present on both sides of the fuse (from the voltage source and to the load), the fuse is not open. Another method commonly used, is to measure across the fuse with the voltmeter. If NO voltage is indicated on the meter, the fuse is good, (not open).

Remember there is no voltage drop across a straight piece of wire. Some plug-type fuseholders have test points built in to allow you to check the voltage. To check for voltage on a clip-type fuseholder, check each of the clips. The advantage of using a voltmeter to check for an open fuse is that the circuit does not have to be deenergized and the fuse does not have to be removed.

WARNING

PERSONNEL MAY BE EXPOSED TO HAZARDOUS VOLTAGE

p. 122

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-26 UNCLASSIFIED 2.3.1.5.1.4 Safety Precautions when Checking a Fuse Since a fuse has current through it, you must be very careful when checking for an open fuse to avoid being shocked or damaging the circuit. The following safety precautions will protect you and the equipment you are using.

• Turn the power off and discharge the circuit before removing a fuse. • Use a fuse puller (an insulated tool) when you remove a fuse from a clip-type fuseholder. • When you check a fuse with a voltmeter, be careful to avoid shocks and short circuits. • When you use an ohmmeter to check fuses with low current ratings, be careful to avoid opening the fuse by excessive current from the ohmmeter.

Q21. What are three methods for determining if a fuse is open? Q22. You have just checked a fuse with an ohmmeter and find that the fuse is shorted. What should you do? Q23. You have just checked a 1/500-ampere fuse with an ohmmeter and find it is open. Checking the replacement fuse shows the replacement fuse is open also. Why would the replacement fuse indicate open? Q24. How could you check a 1/500-ampere fuse with an ohmmeter? Q25. List the safety precautions to be observed when checking fuses.

p. 123

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-27 UNCLASSIFIED 2.3.1.6 Replacement of Fuses After an open fuse is found and the trouble that caused the fuse to open has been corrected, the fuse must be replaced. Before you replace the fuse, you must be certain the replacement fuse is the proper type and fits correctly.

2.3.1.6.1 Proper Type of Replacement Fuse To be certain a fuse is the proper type, check the technical manual for the equipment. The parts list will show you the proper fuse identification for a replacement fuse. Obtain the exact fuse specified, if possible, and check the identification number of the replacement fuse against the parts list.

If you cannot obtain a direct replacement, use the following guidelines:

• Never use a fuse with a higher current rating, a lower voltage rating, or a slower time delay rating than the specified fuse. • The best substitution fuse is a fuse with the same current and time delay ratings and a higher voltage rating. • If a lower current rating or a faster time delay rating is used, the fuse may open under normal circuit conditions. • Substitute fuses must have the same style (physical dimensions) as the specified fuse.

2.3.1.6.2 Proper Fit of Replacement Fuses When you have obtained a proper replacement fuse, you must make certain it will fit correctly in the fuseholder. If the fuseholder is corroded, the fuse will not fit properly. In addition, the corrosion can cause increased resistance or heating. Clean corroded terminals with fine sandpaper so that all corrosion is removed. Do NOT lubricate the terminals. If the terminals are badly pitted, replace the fuseholder. Be certain the replacement fuseholder is the correct size and type by checking the parts list in the technical manual for the equipment.

After you check for and correct any corrosion problems, be certain the fuse fits tightly in the fuseholder. When you insert the fuse in the cap of a plug-type fuseholder, the fuse should fit tightly. A small amount of pressure should be needed to insert the fuse and cap into the fuseholder body.

p. 124

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-28 UNCLASSIFIED In clip-type fuseholders, the clips can be easily bent out of shape. This causes an incorrect fit, which in time could cause an equipment malfunction. Figure 2-14 shows examples of correct and incorrect fuse contacts for clip-type fuseholders used with knifeblade and ferrule cartridge fuses. The clips shown in the left picture of each row have the correct contact. The three pictures on the right of each row show incorrect contact. Notice how the clips are not contacting completely with the knifeblade or ferrules. This incomplete contact can cause corrosion at the contacts, which in turn can create a high resistance and drop some of the circuit voltage at this point.

If the fuse clips do not make complete contact with the fuse, try to bend the clips back into shape. If the clips cannot be repaired by bending, replace the fuseholder or use clip clamps. Clip clamps are shown in figure 2-15.

Figure 2-14 Contact between clips and fuses

p. 125

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-29 UNCLASSIFIED

The following safety precautions will prevent injury to personnel and damage to equipment. These are the MINIMUM safety precautions for replacing fuses.

• Be sure the power is off in the circuit and the circuit is discharged before replacing a fuse. • Use an identical replacement fuse if possible. • Remove any corrosion from the fuseholder before replacing the fuse. • Be certain the fuse properly fits the fuseholder.

Figure 2-15 Clip clamps

p. 126

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-30 UNCLASSIFIED 2.3.1.7 Preventive Maintenance of Fuses Preventive maintenance of fuses consists of checking for the following conditions and correcting any discrepancies.

1. IMPROPER FUSE. Check the fuse installed against that recommended in the technical manual for the equipment. If an incorrect fuse is installed, replace it with the correct fuse. 2. CORROSION. Check for corrosion on the fuseholder terminals or the fuse itself. If corrosion is present, remove it with fine sandpaper. 3. IMPROPER FIT. Check for contact between the fuse and fuseholder. If a piece of paper will fit between the fuse and the clips on a clip-type fuseholder, there is improper contact. If the fuse is not held in the cap of a plug-type fuseholder, the contacts are too loose. 4. OPEN FUSES. Check fuses for opens. If any fuse is open, repair the trouble that caused the open fuse and replace the fuse.

Q26. You have removed an open fuse from a fuseholder and repaired the cause of the fuse opening. The parts list specifies a fuse coded 𝐹02𝐵125𝑉 1 2 𝐴. There are no fuses available with that identification. In the following list, indicate if the fuse is a direct replacement, a good substitute, or not acceptable. For the fuses that are good substitutes, number them in order of preference and explain why they are numbered that way. If the fuse is not acceptable, explain why.

(a) 𝐹03𝐵125𝑉 1 2 𝐴

(b) 𝐹02𝐵125𝑉 3 8 𝐴

(c) F02GR500B

(d) 𝐹02𝐵32𝑉 1 2 𝐴

(e) F02DR500B

(f) 𝐹02𝐴250𝑉 5 8 𝐴

(g) 𝐹02𝐴125𝑉 1 2 𝐴

p. 127

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-31 UNCLASSIFIED Q27. What two things should you check before replacing a fuse?

Q28. List the safety precautions to be observed when replacing a fuse.

Q29. What conditions should you check for when conducting preventive maintenance on fuses?

p. 128

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-32 UNCLASSIFIED 2.3.2 Circuit Breakers A circuit breaker is a circuit protection device that, like a fuse, will stop current in the circuit if there is a direct short, excessive current, or excessive heat. Unlike a fuse, a circuit breaker is reusable. The circuit breaker does not have to be replaced after it has opened or broken the circuit. Instead of replacing the circuit breaker, you reset it.

Circuit breakers can also be used as circuit control devices. By manually opening and closing the contacts of a circuit breaker, you can switch the power on and off. Circuit control devices will be covered in more detail in the next chapter.

Circuit breakers are available in a great variety of sizes and types. It would not be possible to describe every type of circuit breaker in use today, but this chapter will describe the basic types of circuit breakers and their operational principles.

Circuit breakers have five main components, as shown in figure 2-16. The components are the frame, the operating mechanism, the arc extinguishers and contacts, the terminal connectors, and the trip elements.

Figure 2-16 Circuit breaker components

p. 129

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-33 UNCLASSIFIED The FRAME provides an insulated housing and is used to mount the circuit breaker components (fig. 2-17). The frame determines the physical size of the circuit breaker and the maximum allowable voltage and current.

The OPERATING MECHANISM provides a means of opening and closing the breaker contacts (turning, the circuit ON and OFF). The toggle mechanism shown in figure 2-17 is the quick-make, quick-break type, which means the contacts snap open or closed quickly, regardless of how fast the handle is moved. In addition to indicating whether the breaker is ON or OFF, the operating mechanism handle indicates when the breaker has opened automatically (tripped) by moving to a position between ON and OFF. To reset the circuit breaker, the handle must first be moved to the OFF position, and then to the ON position.

Figure 2-17 Circuit breaker construction

p. 130

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-34 UNCLASSIFIED The ARC EXTINGUISHER confines, divides, and extinguishes the arc drawn between contacts each time the circuit breaker interrupts current. The arc extinguisher is actually a series of contacts that open gradually, dividing the arc and making it easier to confine and extinguish. This is shown in figure 2-18. Arc extinguishers are generally used in circuit breakers that control a large amount of power, such as those found in power distribution panels. Small power circuit breakers (such as those found in lighting panels) may not have arc extinguishers.

TERMINAL CONNECTORS are used to connect the circuit breaker to the power source and the load. They are electrically connected to the contacts of the circuit breaker and provide the means of connecting the circuit breaker to the circuit.

The TRIP ELEMENT is the part of the circuit breaker that senses the overload condition and causes the circuit breaker to trip or break the circuit. This chapter will cover the thermal, magnetic, and thermal magnetic trip units used by most circuit breakers. (Some circuit breakers make use of solid-state trip units using current transformers and solid- state circuitry.)

Figure 2-18 Arc extinguisher action

p. 131

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-35 UNCLASSIFIED 2.3.2.1 Thermal Trip Element A thermal trip element circuit breaker uses a bimetallic element that is heated by the load current. The bimetallic element is made from strips of two different metals bonded together. The metals expand at different rates as they are heated. This causes the bimetallic element to bend as it is heated by the current going to the load. Figure 2-19 shows how this can be used to trip the circuit breaker.

Figure 2-19, view A, shows the trip element with normal current. The bimetallic element is not heated excessively and does not bend. If the current increases (or the temperature around the circuit breaker increases), the bimetallic element bends, pushes against the trip bar, and releases the latch. Then, the contacts open, as shown in figure 2-19, view B.

The amount of time it takes for the bimetallic element to bend and trip the circuit breaker depends on the amount the element is heated. A large overload will heat the element quickly. A small overload will require a longer time to trip the circuit breaker.

Figure 2-19 Thermal trip element action: A. Trip element with normal current; B. Contacts open

p. 132

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-36 UNCLASSIFIED 2.3.2.2 Magnetic Trip Element A magnetic trip element circuit breaker uses an electromagnet in series with the circuit load as in figure 2-20. With normal current, the electromagnet will not have enough attraction to the trip bar to move it, and the contacts will remain closed as shown in figure 2-20, view A. The strength of the magnetic field of the electromagnet increases as current through the coil increases. As soon as the current in the circuit becomes large enough, the trip bar is pulled toward the magnetic element (electromagnet), the contacts are opened, and the current stops, as shown in figure 2-20, view B.

The amount of current needed to trip the circuit breaker depends on the size of the gap between the trip bar and the magnetic element. On some circuit breakers, this gap (and therefore the trip current) is adjustable.

Figure 2-20 Magnetic trip element action; Closed contacts

p. 133

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-37 UNCLASSIFIED 2.3.2.3 Thermal-Magnetic Trip Element The thermal trip element circuit breaker, like a delay fuse, will protect a circuit against a small overload that continues for a long time. The larger the overload, the faster the circuit breaker will trip. The thermal element will also protect the circuit against temperature increases. A magnetic circuit breaker will trip instantly when the preset current is present. In some applications, both types of protection are desired. Rather than use two separate circuit breakers, a single trip element combining thermal and magnetic trip elements is used. A thermal-magnetic trip element is shown in figure 2-21.

In the thermal-magnetic trip element circuit breaker, a magnetic element (electromagnet) is connected in series with the circuit load, and a bimetallic element is heated by the load current. With normal circuit current, the bimetallic element does not bend, and the magnetic element does not attract the trip bar, as shown in figure 2-21, view A.

Figure 2-21 Thermal-magnetic element action

p. 134

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-38 UNCLASSIFIED If the temperature or current increases over a sustained period of time, the bimetallic element will bend, push the trip bar and release the latch. The circuit breaker will trip as shown in figure 2-21, view B.

If the current suddenly or rapidly increases enough, the magnetic element will attract the trip bar, release the latch, and the circuit breaker will trip, as shown in figure 2-21, view C. (This circuit breaker has tripped even though the thermal element has not had time to react to the increased current.)

Q30. What are the five main components of a circuit breaker? Q31. What are the three types of circuit breaker trip elements? Q32. How does each type of trip element react to an overload? 2.3.2.4 Trip-Free/Nontrip-Free Circuit Breakers Circuit breakers are classified as being trip free or nontrip free. A trip-free circuit breaker is a circuit breaker that will trip (open) even if the operating mechanism (ON-OFF switch) is held in the ON position. A nontrip-free circuit breaker can be reset and/or held ON even if an overload or excessive heat condition is present. In other words, a nontrip- free circuit breaker can be bypassed by holding the operating mechanism ON.

Trip-free circuit breakers are used on circuits that cannot tolerate overloads and on non- emergency circuits. Examples of these are precision or current sensitive circuits, non- emergency lighting circuits, and nonessential equipment circuits. Nontrip-free circuit breakers are used for circuits that are essential for operations. Examples of these circuits are emergency lighting, required control circuits, and essential equipment circuits.

p. 135

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-39 UNCLASSIFIED 2.3.2.5 Time Delay Ratings Circuit breakers, like fuses, are rated by the amount of time delay. In circuit breakers the ratings are instantaneous, short time delay, and longtime delay. The delay times of circuit breakers can be used to provide for SELECTIVE TRIPPING.

Selective tripping is used to cause the circuit breaker closest to the faulty circuit to trip. This will remove power from the faulty circuit without affecting other, non-faulty circuits. Figure 2-22 should help you understand selective tripping.

Figure 2-22 shows a power distribution system using circuit breakers for protection. Circuit breaker 1 (CB1) has the entire current for all seven loads through it. CB2 feeds loads 1, 2, 3, and 4 (through CB4, CB5, CB6, and CB7), and CB3 feeds loads 5, 6, and 7 (through CB8, CB9, and CB10). If all the circuit breakers were rated with the same time delay, an overload on load 5 could cause CB1, CB3, and CB8 to trip. This would remove power from all seven loads, even though load 5 was the only circuit with an overload.

Figure 2-22 Use of circuit breakers in a power distribution system

p. 136

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-40 UNCLASSIFIED Selective tripping would have CB1 rated as long time delay, CB2 and CB3 rated as short time delay, and CB4 through CB10 rated as instantaneous. With this arrangement, if load 5 had an overload, only CB8 would trip. CB8 would remove the power from load 5 before CB1 or CB3 could react to the overload. In this way, only load 5 would be affected and the other circuits would continue to operate.

2.3.2.6 Physical Types of Circuit Breakers All the circuit breakers presented so far in this chapter have been physically large, designed to control large amounts of power, and used a type of toggle operating mechanism. Not all circuit breakers are of this type. The circuit breaker in figure 2-23 is physically large and controls large amounts of power; but the operating mechanism is not a toggle. Except for the difference in the operating mechanism, this circuit breaker is identical to the circuit breakers already presented.

Figure 2-23 Circuit breaker with an operating handle

p. 137

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-41 UNCLASSIFIED Circuit breakers used for low power protection, such as 28-volt dc, 30 amperes, can be physically small. With low power use, arc extinguishers are not required, and so are not used in the construction of these circuit breakers. Figure 2-24 shows a low power circuit breaker of the push-button or push-pull type. This circuit breaker has a thermal trip element (the bimetallic disk) and is nontrip-free. The push button is the operating mechanism of this circuit breaker.

Q33. What is a trip-free circuit breaker? Q34. What is a nontrip-free circuit breaker? Q35. Where should you use a trip-free circuit breaker? Q36. Where should you use a nontrip-free circuit breaker? The magnetic trip element makes use of a magnetic element (electromagnet). If current reaches a preset quantity, the magnetic element attracts the trip bar and releases the latch.

The thermal-magnetic trip element combines the actions of the bimetallic and magnetic elements in a single trip element. If either the bimetal element or the magnetic element reacts, the circuit breaker will trip.

Figure 2-24 Push-button circuit breaker

p. 138

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-42 UNCLASSIFIED Q37. What are the three time delay ratings for circuit breakers? Q38. What is selective tripping and why is it used? Q39. If the power distribution system shown in figure 2-22 uses selective tripping, what is the time delay rating for each of the circuit breakers shown? Q40. What factors are used to select a circuit breaker? Q41. What type of circuit breaker is used on a multimeter? 2.3.2.7 Circuit Breaker Maintenance Circuit breakers require careful inspection and periodic cleaning. Before you attempt to work on circuit breakers, check the applicable technical manual carefully. When you work on shipboard circuit breakers, the approval of the electrical or engineering officer must be obtained before starting work. Be certain to remove all power to the circuit breaker before you work on it. Tag the switch that removes the power to the circuit breaker to ensure that power is not applied while you are working.

Once approval has been obtained, the incoming power has been removed, the switch tagged, and you have checked the technical manual, you may begin to check the circuit breaker. Manually operate the circuit breaker several times to be sure the operating mechanism works smoothly. Inspect the contacts for pitting caused by arcing or corrosion. If pitting is present, smooth the contacts with a fine file or number 00 sandpaper. Be certain the contacts make proper contact when the operating mechanism is ON.

Check the connections at the terminals to be certain the terminals and wiring are tight and free from corrosion. Check all mounting hardware for tightness and wear. Check all components for wear. Clean the circuit breaker completely.

When you have finished working on the circuit breaker, restore power and remove the tag from the switch that applies power to the circuit.

p. 139

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-43 UNCLASSIFIED Q42. What steps are to be taken before beginning work on a circuit breaker? Q43. What items are you to check when working on a circuit breaker? 2.4 SUMMARY This chapter has provided the information to enable you to have a basic understanding of circuit protection devices. The following is a summary of the main points in this chapter.

CIRCUIT PROTECTION DEVICES are needed to protect personnel and circuits from hazardous conditions. The hazardous conditions can be caused by a direct short, excessive current or excessive heat. Circuit protection devices are always connected in series with the circuit being protected.

A DIRECT SHORT is a condition in which some point in the circuit, where full system voltage is present, comes in direct contact with the ground or return side of the circuit.

EXCESSIVE CURRENT describes a condition that is not a direct short but in which circuit current increases beyond the designed current carrying ability of the circuit.

EXCESSIVE HEAT describes a condition in which the heat in or around a circuit increases to a higher than normal level.

FUSES and CIRCUIT BREAKERS are the two types of circuit protection devices discussed in this chapter.

PLUG-TYPE FUSES are used in low-voltage, low-current circuits. This type fuse is rapidly being replaced by the circuit breaker.

CARTRIDGE FUSES are available in a wide range of physical sizes and voltage and current ratings. This type fuse is the most commonly used fuse.

The CURRENT RATING of a fuse is a value expressed in amperes that represents the amount of current the fuse will allow to flow without opening.

The VOLTAGE RATING of a fuse indicates the ability of the fuse to quickly extinguish the arc after the fuse element melts and the maximum voltage the open fuse will block.

p. 140

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-44 UNCLASSIFIED The TIME DELAY RATING of a fuse indicates the relationship between the current through the fuse and the time it takes for the fuse to open. The three time delay ratings for fuses are DELAY, STANDARD, and FAST.

DELAY FUSES allow surge currents without opening. They are used to protect motors, solenoids, and transformers.

STANDARD FUSES have neither a time delay nor a fast acting characteristic. They are used in automobiles, lighting circuits and electrical power circuits.

FAST FUSES open very quickly with any current above the current rating of the fuse. They are used to protect delicate instruments or semiconductor devices.

The OLD MILITARY FUSE DESIGNATION is a system of fuse identification that uses coding to represent the current, voltage, and time-delay rating of the fuse. New fuses purchased by the Navy will no longer use this designation.

The NEW MILITARY FUSE DESIGNATION is the system used to identify fuses purchased by the Navy at the present time. The coding of current and voltage ratings has been replaced with direct printing of these ratings.

The OLD COMMERCIAL FUSE DESIGNATION was used by the fuse manufacturers to identify fuses. The current and voltage ratings are printed on the fuse, but the time delay rating is contained in the style coding of the fuse.

The NEW COMMERCIAL FUSE DESIGNATION is currently used by fuse manufacturers to identify fuses. It is similar to the old commercial fuse designation with the difference being in the style coding portion of the designation.

FUSEHOLDERS are used to allow easy replacement of fuses in a circuit.

The CLIP-TYPE has clips to connect the ferrules or knife-blades of the fuse to the circuit. The POST-TYPE is an enclosed fuseholder. The center connection of the post type should be connected to the power source and the outside connector should be connected to the load.

p. 141

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-45 UNCLASSIFIED OPEN FUSES can be found by VISUAL INSPECTION, FUSE INDICATORS, or by the use of a METER. The following SAFETY PRECAUTIONS should be observed when checking a fuse:

• Turn the power off and discharge the circuit before removing a FUSE. • Use a fuse puller when you remove a fuse from clip-type fuseholders. • When you check a fuse with a voltmeter, be careful to avoid shocks and short circuits. • When you use an ohmmeter to check fuses with low current ratings, be careful to avoid opening the fuse by excessive current.

REPLACEMENT FUSES must be of the proper type. Check the technical manual parts list to find the identification of the proper fuse. If a substitute fuse must be used, the following guidelines should be followed:

• Never use a fuse with a higher current rating, a lower voltage rating, or a slower time delay rating than the specified fuse. • The best substitution fuse is a fuse with the same current and time delay ratings and a higher voltage rating. • If a lower current rating, or a lower time delay rating is used, the fuse may open under normal circuit conditions. Substitute fuses must have the same style (physical dimensions) as the specified fuse.

PROPER FIT between the fuse and fuseholder is essential. If the clips on clip-type fuseholders are sprung, the clips should be reformed, or clip clamps should be used. Any corrosion on fuses or fuseholders must be removed with fine sandpaper.

PREVENTIVE MAINTENANCE of fuses involves checking for the proper fuse, corrosion, proper fit, and open fuses; and correcting any discrepancies.

CIRCUIT BREAKERS have five main components: The frame, the operating mechanism, the arc extinguisher, the terminal connectors, and the trip element.

A THERMAL TRIP ELEMENT uses a bimetallic element that is heated by load current and bends due to this heating. If current (or temperature) increases above normal, the bimetallic element bends to push against a trip bar and opens the circuit.

A MAGNETIC TRIP ELEMENT uses an electromagnet in series with the load current to attract the trip bar and open the circuit if excessive current is present.

A THERMAL-MAGNETIC TRIP ELEMENT combines the thermal and magnetic trip elements into a single unit. A TRIP-FREE circuit breaker will trip (open) even if the operating mechanism is held in the ON position. A TRIP-FREE circuit breaker would be used on non-essential circuits.

p. 142

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-46 UNCLASSIFIED A NONTRIP-FREE circuit breaker can be bypassed by holding the operating mechanism ON. A NONTRIP-FREE circuit breaker would be used for emergency or essential equipment circuits.

The TIME DELAY RATINGS of circuit breakers are INSTANTANEOUS, SHORT TIME DELAY, and LONG TIME DELAY.

SELECTIVE TRIPPING is used to cause the circuit breaker closest to the faulty circuit to trip, isolating the faulty circuit without affecting other non-faulty circuits. This is accomplished by using an instantaneous circuit breaker close to the load, a short time delay circuit breaker at the next junction, and a long time delay circuit breaker at the main junction box.

The FACTORS used to select a circuit breaker are the power requirements of the circuit and the physical space available.

When WORKING ON CIRCUIT BREAKERS, the following items should be done BEFORE working on the circuit breaker: Check the applicable technical manual, obtain the approval of the electrical or engineering officer (for shipboard circuit breakers), remove power from the circuit breaker, and tag the switch that removes power from the circuit breaker. The following items should be checked and discrepancies corrected when working on circuit breakers: Check the operating mechanism for smooth operation, check the contacts for pitting, check the terminals for tightness and corrosion, check the mounting hardware for tightness and wear, check all components for wear, and check the entire circuit breaker for cleanliness.

p. 143

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-47 UNCLASSIFIED ANSWERS TO QUESTIONS Q1. THROUGH Q43.

A1. To protect people and circuits from possible hazardous conditions.

A2. A direct short, excessive current, and excessive heat.

A3. A condition in which some point in the circuit where full system voltage is present comes in contact with the ground or return side of the circuit.

A4. A condition that is not a direct short but in which circuit current increases beyond the designed current carrying ability of the circuit.

A5. A condition in which the heat in or around the circuit increases to a higher than normal level

A6. In series, so total current will be stopped when the device opens.

A7. Fuses and circuit breakers.

A8.

a. circuit breaker b. fuse.

A9.

a. cartridge b. plug c. plug d. cartridge.

A10. A, C.

A11. Current, voltage, and time delay.

A12. The amount of current the fuse will allow without opening.

A13. The ability of the fuse to quickly extinguish the arc after the fuse element melts and the maximum voltage that cannot jump across the gap of the fuse after the fuse opens.

A14. Delay, standard, and fast.

A15. Delay-Motors, solenoids, or transformers. Standard-Automobiles, lighting or electrical power circuits. Fast-Delicate instruments or semiconductor devices.

p. 144

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-48 UNCLASSIFIED A16.

a. 125 volts or less, 1.5 amperes, delay b. 250 volts or less, 1/8 ampere standard

A17.

a. 125 volts or less, 1/16 ampere b. 250 volts or less, .15 ampere

A18. F05B32V20A.

A19.

a. Post-type fuseholder b. Clip-type fuseholder

A20.

a. Center connector b. Outside connector

A21. Visual inspection, indicators, and using a meter.

A22. Put it back in the circuit. A good fuse will have zero ohms of resistance.

A23. The ohmmeter causes more than 1/500 ampere through the fuse when you check the fuse, thus it opens the fuse.

A24. Use a resistor in series with the fuse when you check it with the ohmmeter.

A25. Turn the power off and discharge the circuit before you remove fuses. Use a fuse puller (an insulated tool) when you remove fuses front clip-type fuse holders. When you check fuses with a voltmeter, be careful to avoid shocks and short circuits.

A26.

a. Not acceptable-wrong style b. Substitute #3-smaller current rating c. Substitute #1-identical, except higher voltage rating d. Not acceptable-lower voltage rating e. Direct replacement f. Not acceptable-higher current rating g. Substitute #2-Faster time delay rating

p. 145

NEETS Module 3, NAVEDTRA 14175A UNCLASSIFIED

2-49 UNCLASSIFIED A27. Check for the proper type of replacement fuse and proper fit.

A28. Be sure the power is off in the circuit and the circuit is discharged before replacing a fuse. Use an identical replacement fuse if possible. Remove any corrosion from the fuseholders before replacing the fuses.

A29. Improper fuse, corrosion, improper fit, and open fuse.

A30. Frame, operating mechanism, arc extinguishers, terminal connectors, and trip element.

A31. Thermal, magnetic, and thermal-magnetic.

A32. The thermal trip element makes use of a bimetallic element that bends with an increase in temperature or current. The bending causes the trip bar to be moved releasing the latch.

A33. A circuit breaker that will trip even if the operating mechanism is held ON.

A34. A circuit breaker that can be overridden if the operating mechanism is held ON.

A35. In current sensitive or nonemergency systems.

A36. In emergency or essential circuits.

A37. Instantaneous, short time delay, and long time delay.

A38. It is the use of time delay ratings to cause the circuit breaker closest to the faulty circuit to trip. This isolates the faulty circuit without affecting other circuits.

A39. CB1-long time delay; CB2, CB3-short time delay; CB4 through CB10- instantaneous.

A40. The power requirements of the circuit and the physical space available.

A41. A push button or push-pull circuit breaker (small size, low power).

A42. Check the applicable technical manual, obtain the approval of the electrical or engineering officer (for shipboard circuit breakers), remove power from the circuit breaker, and tag the switch that supplies power to the circuit breaker.

A43. Check the operating mechanism for smooth operation, check the contacts for pitting, check the terminals for tightness and corrosion, check the mounting hardware for tightness and wear, check all components for wear, and check the entire circuit breaker for cleanliness.